Sprinkler Identification Numbers

This searchable list connects contractors and facility managers with a match for existing sprinklers and accessories

Every fire sprinkler manufactured in the past 19 years has a sprinkler identification number (SIN). And when it comes to replacing an existing head—or locating compatible accessories, like escutcheons, wrenches, or cover plates—the SIN provides an essential starting point.

This guide—and the accompanying directory—was created to:

  • Help consumers quickly understand essential characteristics of their sprinklers
  • Make finding a substitute for discontinued heads simple
  • Connect buyers to identical sprinklers and compatible accessories

To do that, we've grouped similar types of fire sprinkler heads together across four leading manufacturers: Senju Sprinkler, Tyco, Victaulic, and Viking. Each entry includes the SIN, the manufacturer's part number(s), thread size, K-factor (orifice size), and a basic description. If you have a sprinkler identification number handy, you can either:

  • Search for it by pressing Control-F (Windows) or Command-F (Mac). Type in the SIN to find a match. Once you find it, click on the link in the table to run a search of QRFS’s inventory for sprinklers and compatible accessories.
  • Browse by category using our table of contents

You're welcome to skip ahead, but be warned: knowing the SIN may not be enough. While each SIN refers to very specific sprinkler head types, or models, it doesn't specify a temperature or finish. If you'd like an introduction (or a refresher), read on before browsing or searching our directory.

You can check out our online selection of sprinklers, escutcheons, cover plates, wrenches, and more.

Sprinkler identification numbers specify a model but not an exact match, leaving consumers and contractors with some challenges

Sprinkler identification numbers help to distinguish between different types of fire sprinklers—but they're not always enough

Here's why you really need to know about SINs: leading fire codes require an exact or nearly exact match between sprinklers and common accessories. A broken or damaged cover plate needs the manufacturer's recommended replacement. The same goes for many escutcheons (sometimes called "trim plates"). Even the wrenches kept in spare sprinkler cabinets should be "specified by the manufacturer." The SIN helps consumers track down compatible parts or, in the case of broken/obsolete sprinklers, acceptable substitutes.

Let's get to it: a sprinkler identification number consists of one or two letters followed by three or four numbers. That code is imprinted on each sprinkler's deflector—the thin metallic part furthest away from a sprinkler's threaded inlet. Today, they're everywhere, thanks to recommendations from the National Fire Protection Association (NFPA). And guidelines from the International Fire Suppression Alliance (IFSA) require a new SIN for each variation in:

  • Orifice size (K-factor)
  • Response type (with "quick response" and "standard response" as the two leading kinds)
  • Distribution characteristic (including whether a sprinkler stands upright, points down, or mounts sideways)
  • Maximum working pressure

But one SIN may encompass several different temperature ratings, finishes, and approvals. (To get an exact match, you'll want to follow the steps outlined in our guide to sprinkler replacement). Further, these codes aren't uniform. Each one-or-two-letter prefix represents a manufacturer. Some of those prefixes include:

  • C, CS: Central Sprinkler
  • F, G: Grinnell Corporation
  • GL, GS: Globe Fire Sprinkler
  • GV: Victaulic Company
  • R, RA: The Reliable Automatic Sprinkler Co., Inc.
  • S: Star Sprinkler Inc.
  • SS: Senju Sprinkler Co., Ltd.
  • TF, TY: Tyco Fire/Tyco International
  • V: Victaulic Company
  • VK: The Viking Corporation Ltd.

However, the numbers that follow are assigned as that manufacturer sees fit. For example, VK101, V101, and SS101—Viking, Victaulic, and Senju sprinklers, respectively—may have nothing in common, other than the fact that they're all sprinklers.

Picture of Tyco Fire Sprinklers

All three of these sprinklers share the same SIN—TY315—but activate at significantly different temperatures (as their colored bulbs indicate).

Our directory lists major types of fire sprinklers along with key ordering information

At the time of writing, there doesn't appear to be a single, open-access database for the world's sprinkler identification numbers. Some offerings come close: Product iQ™, a database operated by the safety science giant UL, allows (registered) users to search a list of their certified sprinklers.

In an effort to fill that gap, we've created a directory that separates SINs by sprinkler-head type. For the most part, these are organized by the sprinkler's K-factor, which measures how much water passes through the sprinkler. It's one of a few "operating characteristics" that must remain the same whenever a sprinkler is replaced. Sorting by K-factor makes it easier to find that match.

If the exact model isn't available, another brand or model may work as long as it has the same:

  • Temperature rating
  • Style and design requirements (is it a storage sprinkler, for example?)
  • Deflector type (is it a pendent, upright, or horizontal sidewall head?)
  • Special coatings (such as those that resist chemical corrosion)

If you find the sprinkler identification number you're looking for, click on the SIN for a list of sprinklers and related products in stock at QRFS.

If you find it helpful, feel free to check us out at Facebook.com/QuickResponseFireSupply or on Twitter @QuickResponseFS to stay up to date on other articles.

Remember, the easiest way to use the below table is to search for your SIN by pressing Control-F (Windows) or Command-F (Mac). Type in the SIN to find a match. Once you find it, click on the link to see a search of QRFS for sprinklers and compatible accessories.

Browse by Category and Sprinkler Identification Number (SIN)

Standard (Wet) Commercial Heads

Residential Heads

Dry Sprinklers

Specialty Heads

SINs and Descriptions for Commercial Fire Sprinklers

Commercial: Under 5.6K (Grouped by K-Factor, Sorted by Sprinkler Identification Number)

SIN Manufacturer Part Number K-Factor Thread Description
TY1131 Tyco 57-330-1-135 2.8 1/2" NPT TY-FRB 3mm Bulb Quick Response Upright
TY1231 Tyco 57-331-1-135 2.8 1/2" NPT TY-FRB 3mm Bulb Quick Response Recessed Pendent
V2701 Victaulic V2701 2.8 1/2" NPT Standard Commercial Upright: Standard Response
V2702 Victaulic V2702 2.8 1/2" NPT Standard Commercial Upright: Quick Response
V2705 Victaulic V2705 2.8 1/2" NPT Standard Commercial Pendent: Standard Response
V2706 Victaulic V2706 2.8 1/2" NPT Standard Commercial Pendent: Quick Response
VK325 Viking 06717B, 12980 2.8 1/2" NPT Quick Response Upright, Small Orifice
VK326 Viking 13956, 13957 2.8 1/2" NPT Quick Response Fusible Element Upright, Small Orifice
VK329 Viking 06718B, 12981 2.8 1/2" NPT Quick Response Pendent, Small Orifice
VK330 Viking 13959, 13960 2.8 1/2" NPT Quick Response Fusible Element Pendent, Small Orifice
VK333 Viking 10035 2.8 1/2" NPT Quick Response Horizontal Sidewall, Small Orifice
VK334 Viking 13962 2.8 1/2" NPT Quick Response Fusible Element Horizontal Sidewall, Small Orifice
VK341 Viking 13963 2.8 1/2" NPT Quick Response Upright, Small Orifice
VK461 Viking 13831A 2.8 1/2" NPT Standard/Quick Response Concealed Pendent, Small Orifice
TY2131 Tyco 57-340-1-135 4.2 1/2" NPT TY-FRB 3mm Bulb Quick Response Upright
TY2231 Tyco 57-341-1-135 4.2 1/2" NPT TY-FRB 3mm Bulb Quick Response Recessed Pendent
V2401 Victaulic V2401 4.2 3/8" NPT Standard Commercial Upright: Standard Response
V2402 Victaulic V2402 4.2 3/8" NPT Standard Commercial Upright: Quick Response
V2403 Victaulic V2403 4.2 3/8" NPT Standard Commercial Pendent: Standard Response
V2404 Victaulic V2404 4.2 3/8" NPT Standard Commercial Pendent: Quick Response
VK004 Viking 10222 4.2 1/2" NPT Standard Response Pendent, Small Orifice
VK006 Viking 5574 4.2 1/2" NPT Standard Response Fusible Link Upright, Small Orifice
VK008 Viking 5575 4.2 1/2" NPT Standard Response Fusible Link Pendent, Small Orifice
VK327 Viking 06719B 4.2 1/2" NPT Quick Response Upright, Small Orifice
VK328 Viking 13958 4.2 1/2" NPT Quick Response Upright, Small Orifice
VK331 Viking 06720B 4.2 1/2" NPT Quick Response Pendent, Small Orifice
VK332 Viking 13961 4.2 1/2" NPT Quick Response Fusible Element Pendent, Small Orifice
VK465 Viking 14262A 4.2 1/2" NPT Quick Response Concealed Pendent, Small Orifice

Return to the table of contents or contact us with questions.

 

Commercial: 5.6K

SIN Manufacturer Part Number K-Factor Thread Description
SS2521 Senju SS2521 5.6 1/2" NPT Commercial Horizontal Sidewall: Quick Response
SS2551 Senju SS2551 5.6 1/2" NPT Commercial Pendent, Recessed Pendent: Quick Response
SS2552 Senju SS2552 5.6 1/2" NPT Commercial Upright: Quick Response
SS9521 Senju SS9521 5.6 1/2" NPT Commercial Horizontal Sidewall: Quick Response
SS9561 Senju SS9561 5.6 1/2" NPT Commercial Horizontal Sidewall: Quick Response
TY313 Tyco 77-370-1-135 5.6 1/2" NPT TY-FRB 3mm Bulb Quick Response Upright
TY3131 Tyco 57-370-2-XXX 5.6 1/2" NPT TY-FRB Upright Quick Response Poly-Stainless Grey
TY3133 Tyco 57-333-1-135 5.6 1/2" NPT TY-FRB 3mm Bulb Quick Response Upright w/Shield
TY3151 Tyco 77-570-1-135 5.6 1/2" NPT TY-B 5mm Bulb Upright
TY3151 Tyco 57-570-2-XXX 5.6 1/2" NPT TY-B Upright Standard Response Poly-Stainless Grey
TY3153 Tyco 57-533-1-135 5.6 1/2" NPT TY-B 5mm Bulb Upright w/Shield
TY323 Tyco 77-371-1-135 5.6 1/2" NPT TY-FRB 3mm Bulb Quick Response Recessed Pendent
TY3231 Tyco 57-371-2-XXX 5.6 1/2" NPT TY-FRB Pendent Quick Response Poly-Stainless Grey
TY3231 Tyco 57-333-1-155 5.6 1/2" NPT TY-FRB 3mm Bulb Quick Response Upright w/Shield
TY3251 Tyco 77-571-1-135 5.6 1/2" NPT TY-B 5mm Bulb Recessed Pendent
TY3251 Tyco 57-571-2-XXX 5.6 1/2" NPT TY-B Pendent Standard Response Poly-Stainless Grey
TY3331 Tyco 57-378-2-XXX 5.6 1/2" NPT TY-FRB Horizontal Sidewall Quick Response Poly-Stainless Grey
TY3331 Tyco 57-378-1-135 5.6 1/2" NPT TY-FRB 3mm Bulb Quick Response Recessed Horizontal Sidewall
TY3332 Tyco 57-376-1-135 5.6 1/2" NPT TY-FRB 3 mm Bulb Quick Response Horizontal Sidewall
TY3351 Tyco 57-578-2-XXX 5.6 1/2" NPT TY-B Horizontal Sidewall Standard Response Poly-Stainless Grey
TY3351 Tyco 57-578-1-135 5.6 1/2" NPT TY-B 5mm Bulb Recessed Horizontal Sidewall
TY3431 Tyco 57-375-1-135 5.6 1/2" NPT TY-FRB 3mm Bulb Quick Response Vertical Sidewall
TY3451 Tyco 57-575-1-135 5.6 1/2" NPT TY-B 5mm Bulb Vertical Sidewall
TY3531 Tyco 51-792-1-155 5.6 1/2" NPT RFII Quick Response Pendent Concealed
TY3551 Tyco 51-790-1-155 5.6 1/2" NPT RFII Standard Response Pendent Concealed Std. Pressure
TY3631 Tyco 77-373-1-135 5.6 1/2" NPT TY-FRB 3mm Bulb Quick Response Conventional
TY3651 Tyco 77-573-1-135 5.6 1/2" NPT TY-B 5mm Bulb NPT Conventional
V2703 Victaulic V2703 5.6 1/2" NPT Standard Commercial Upright: Standard Response
V2704 Victaulic V2704 5.6 1/2" NPT Standard Commercial Upright: Quick Response
V2707 Victaulic V2707 5.6 1/2" NPT Standard Commercial Pendent: Standard Response
V2708 Victaulic V2708 5.6 1/2" NPT Standard Commercial Pendent: Quick Response
V2709 Victaulic V2709 5.6 1/2" NPT Standard Commercial Horizontal Sidewall: Standard Response
V2710 Victaulic V2710 5.6 1/2" NPT Standard Commercial Horizontal Sidewall: Quick Response
V2725 Victaulic V2725 5.6 1/2" NPT Standard Commercial Conventional: Standard Response
V2726 Victaulic V2726 5.6 1/2" NPT Standard Commercial Conventional: Quick Response
V2727 Victaulic V2727 5.6 1/2" NPT Standard Commercial European Pendent: Standard Response
V2728 Victaulic V2728 5.6 1/2" NPT Standard Commercial European Pendent: Quick Response
V2753 Victaulic V2753 5.6 1/2" NPT Standard Commercial Conventional: Standard Response
V2754 Victaulic V2754 5.6 1/2" NPT Standard Commercial Conventional: Quick Response
V3801 Victaulic V3801 5.6 1/2" NPT Standard Commercial Concealed Pendent: Standard Response
V3802 Victaulic V3802 5.6 1/2" NPT Standard Commercial Concealed Pendent: Quick Response
V3808 Victaulic V3808 5.6 1/2" NPT Standard Commercial Concealed Pendent: Quick Response
VK100 Viking 10138, 12986 5.6 1/2" NPT Standard Response Upright
VK102 Viking 10139, 12987 5.6 1/2" NPT Standard Response Pendent
VK102-D Viking 10139AX 5.6 1/2" NPT Standard Response Domed Concealed Pendent
VK110 Viking 05508, 12972 5.6 1/2" NPT Standard Response Fusible Element Pendent
VK112 Viking 05559, 12974 5.6 1/2" NPT Standard Response Fusible Element Horizontal Sidewall
VK130 Viking 05012B 5.6 1/2" NPT Standard Response Model N-2 Stainless Steel Upright
VK132 Viking 06483B 5.6 1/2" NPT Standard Response Model N-2 Stainless Steel Pendent
VK300 Viking 06661B, 12978 5.6 1/2" NPT Quick Response Upright
VK301 Viking 12279, 17535, 19779 5.6 1/2" NPT Quick Response Fusible Element Upright
VK302 Viking 06662B, 19780, 18021, 12979 5.6 1/2" NPT Quick Response Pendent
VK302-D Viking 06662BAX (Discontinued) 5.6 1/2" NPT Standard/Quick Response Domed Concealed Pendent
VK303 Viking 12275, 17536, 19781 5.6 1/2" NPT Quick Response Fusible Element Pendent
VK304 Viking 12982 5.6 1/2" NPT Quick Response Horizontal Sidewall
VK305 Viking 12121, 19782, 12997 5.6 1/2" NPT Quick Response Horizontal Sidewall
VK306 Viking 06727B, 12983 5.6 1/2" NPT Quick Response Vertical Sidewall
VK307 Viking 13947, 13948 5.6 1/2" NPT Quick Response Fusible Element Horizontal Sidewall
VK308 Viking 13949, 13950 5.6 1/2" NPT Quick Response Fusible Element Horizontal Sidewall
VK309 Viking 13951 5.6 1/2" NPT Quick Response Fusible Element VSW
VK316 Viking 13953 5.6 1/2" NPT Quick Response Fusible Element Upright
VK320 Viking 13955 5.6 1/2" NPT Quick Response Fusible Element Horizontal Sidewall
VK338 Viking 14692 5.6 1/2" NPT Quick Response Stainless Steel Upright
VK339 Viking 14693 5.6 1/2" NPT Quick Response Stainless Steel Pendent
VK400 Viking 06697B 5.6 1/2" NPT Standard Response Model H Fusible Link Flush Pendent, Std. Orifice
VK402 Viking 06702B 5.6 1/2" NPT Quick Response Model H-1 Fusible Link Flush Pendent
VK404 Viking 09783A (Discontinued) 5.6 1/2" NPT Standard Response/Quick Response Model B-2 Fusible Link Concealed Pendent
VK408 Viking 11262A (Discontinued) 5.6 1/2" NPT Quick Response Concealed Horizontal Sidewall Sprinkler, Std. Orifice
VK413 Viking 11487 5.6 1/2" NPT Quick Response Model H Fusible Link Flush Pendent
VK462 Viking 13503A, 19785A 5.6 1/2" NPT Quick Response Concealed Pendent
VK478 Viking 19995 5.6 1/2" NPT Quick Response Flush Pendent
VK481 Viking 17555A 5.6 1/2" NPT Quick Response Concealed Horizontal Sidewall
VK492 Viking 20034 5.6 1/2" NPT Standard Response Concealed Pendent

Return to the table of contents or contact us with questions.

 

Commercial: 8.0K

SIN Manufacturer Part Number K-Factor Thread Description
SS2553 Senju SS2553 8.0 3/4" NPT Commercial Horizontal Sidewall: Quick Response
TY4131 Tyco 57-390-2-XXX 8.0 3/4" NPT TY-FRB Upright Quick Response Poly-Stainless Grey
TY4131 Tyco 57-390-1-135 8.0 3/4" NPT TY-FRB 3mm Bulb Quick Response Upright
TY4133 Tyco 57-343-1-135 8.0 3/4" NPT TY-FRB 3mm Bulb Quick Response Upright w/Shield
TY4151 Tyco 57-590-2-XXX 8.0 3/4" NPT TY-B Upright Standard Response Poly-Stainless Grey
TY4151 Tyco 57-590-1-135 8.0 3/4" NPT TY-B 5mm Bulb Upright
TY4153 Tyco 57-543-1-135 8.0 3/4" NPT TY-B 5mm Bulb Upright w/Shield
TY4231 Tyco 57-391-2-XXX 8.0 3/4" NPT TY-FRB Pendent Quick Response Poly-Stainless Grey
TY4231 Tyco 57-391-1-135 8.0 3/4" NPT TY-FRB 3mm Bulb Quick Response Recessed Pendent
TY4251 Tyco 57-591-2-XXX 8.0 3/4" NPT TY-B Pendent Standard Response Poly-Stainless Grey
TY4251 Tyco 57-591-1-135 8.0 3/4" NPT TY-B 5mm Bulb Recessed Pendent
TY4631 Tyco 57-393-1-135 8.0 3/4" NPT TY-FRB 3mm Bulb Quick Response Conventional
TY4651 Tyco 57-593-1-135 8.0 3/4" NPT TY-B 5mm Bulb NPT Conventional
TY4831 Tyco 57-360-1-135 8.0 1/2" NPT TY-FRB 3mm Bulb Quick Response Upright
TY4851 Tyco 57-560-1-135 8.0 1/2" NPT TY-B 5mm Bulb Upright
TY4931 Tyco 57-361-1-135 8.0 1/2" NPT TY-FRB 3mm Bulb Quick Response Pendent
TY4951 Tyco 57-561-1-135 8.0 1/2" NPT TY-B 5mm Bulb Pendent
V3401 Victaulic V3401 8.0 3/4" NPT Standard Commercial Upright: Standard Response
V3402 Victaulic V3402 8.0 3/4" NPT Standard Commercial Upright: Quick Response
V3405 Victaulic V3405 8.0 3/4" NPT Standard Commercial Pendent: Standard Response
V3406 Victaulic V3406 8.0 3/4" NPT Standard Commercial Recessed Pendent: Quick Response
V3409 Victaulic V3409 8.0 3/4" NPT Standard Commercial Horizontal Sidewall: Standard Response
V3410 Victaulic V3410 8.0 3/4" NPT Standard Commercial Horizontal Sidewall: Quick Response
V3423 Victaulic V3423 8.0 3/4" NPT Standard Commercial European Pendent: Standard Response
V3424 Victaulic V3424 8.0 3/4" NPT Standard Commercial European Pendent: Quick Response
VK200 Viking 10141 8.0 3/4" NPT Standard Response Upright
VK202 Viking 10142 8.0 3/4" NPT Standard Response Pendent
VK202-D Viking 10142AX 8.0 3/4" NPT Standard Response Domed Concealed Pendent
VK204 Viking 5514 8.0 3/4" NPT Standard Response Fusible Link Upright
VK206 Viking 5578 (Retrofit Only) 8.0 1/2" NPT Standard Response Fusible Link Pendent
VK350 Viking 06665B 8.0 3/4" NPT Quick Response Upright
VK351 Viking 13966, 18272 (Both Retrofit Only) 8.0 1/2" NPT Quick Response Fusible Element Upright
VK352 Viking 06666B, 18258, 20383 8.0 3/4" NPT Quick Response Pendent
VK352-D Viking 06666BAX (Discontinued Part Number) 8.0 3/4" NPT Standard/Quick Response Domed Concealed Pendent
VK353 Viking 13975, 18274 8.0 3/4" NPT Quick Response Fusible Element Pendent
VK353-D Viking 13975AX (Discontinued Part Number) 8.0 3/4" NPT Quick Response Concealed Fusible Element Pendent
VK360 Viking 15591 8.0 3/4" NPT Quick Response Horizontal Sidewall
VK464 Viking 13614A 8.0 3/4" NPT Quick Response Concealed Pendent

Return to the table of contents or contact us with questions.

 

SIN Directory for Residential Fire Sprinklers

Residential: Under 5.6K (Grouped by K-Factor and Sorted by SIN)

SIN Manufacturer Part Number K-Factor Thread Description
TY1121 Tyco 58-973-1-165 2.8 1/2" NPT Model TY-FRL Quick Response Upright
TY1221 Tyco 58-981-1-165 2.8 1/2" NPT Model TY-FRL Quick Response Pendent
SS8361 Senju SS8361 3 1/2" NPT Residential Concealed Pendent
VK470 Viking 17147 3 1/2" NPT Residential Pendent
VK4700 Viking 17492 3 1/2" NPT Residential Lead-Free Pendent
VK479 Viking 19707 3 1/2" NPT Residential Horizontal Sidewall
VK488 Viking 18325 3 1/2" NPT Freedom Residential Concealed Pendent
VK4880 Viking 18326 3 1/2" NPT Freedom Residential Lead-Free Concealed Pendent
SS8261 Senju SS8261 3.7 1/2" NPT Residential Concealed Pendent
VK420 Viking 9458 3.8 1/2" NPT Residential Model H-3 Fusible Link Flush Pendent
VK480 Viking 16116AC 4 1/2" NPT Residential Concealed Horizontal Sidewall
VK4800 Viking 16880AC 4 1/2" NPT Residential Lead-Free Concealed Horizontal Sidewall
VK486 Viking 17315 4 1/2" NPT Residential Horizontal Sidewall
SS4421 Senju SS4421 4.2 1/2" NPT Residential Flush Pendent
SS4423 Senju SS4423 4.2 1/2" NPT Residential Flush Horizontal Sidewall
SS4441 Senju SS4441 4.2 1/2" NPT Residential Flush Pendent
TY1334 Tyco 51-211-1-155 4.2 1/2" NPT LFII Low Flow Sidewall
V2738 Victaulic V2738 4.2 1/2" NPT Residential Horizontal Sidewall: Quick Response
VK484 Viking 16240 4.2 1/2" NPT Residential Horizontal Sidewall
VK4840 Viking 16881 4.2 1/2" NPT Residential Lead-Free Horizontal Sidewall
VK430 Viking 9530 4.3 1/2" NPT Residential -4 Pendent
TY2334 Tyco 51-215-1-155 4.4 1/2" NPT LFII Low Flow Sidewall
SS4451 Senju SS4451 4.9 1/2" NPT Residential Pendent/Recessed Pendent
SS8421 Senju SS8421 4.9 1/2" NPT Residential Concealed Pendent
SS8451 Senju SS8451 4.9 1/2" NPT Residential Concealed Pendent
SS8461 Senju SS8461 4.9 1/2" NPT Residential Concealed Pendent
SS8464 Senju SS8464 4.9 1/2" NPT Residential Concealed Pendent
TY2234 Tyco 51-873-1-155 4.9 1/2" NPT LFII Concealed Pendent Domed Plate
TY3596 Tyco 51-112-1-160 4.9 1/2" NPT LFII Residential Concealed
V2740 Victaulic V2740 4.9 1/2" NPT Residential Pendent: Quick Response
V2742 Victaulic V2742 4.9 1/2" NPT Residential Concealed Pendent: Quick Response
VK457 Viking 14694A 4.9 1/2" NPT Residential Fusible Element Concealed Pendent
VK4570 Viking 16872AC 4.9 1/2" NPT Residential Fusible Element Concealed Lead-Free Pendent
VK467 Viking 19154 4.9 1/2" NPT Residential Upright
VK4670 Viking 19442 4.9 1/2" NPT Residential Lead-Free Upright
VK468 Viking 13637 4.9 1/2" NPT Residential Pendent
VK4680 Viking 16876 4.9 1/2" NPT Residential Lead-Free Pendent
VK468-D Viking 13637AX 4.9 1/2" NPT Residential Concealed Pendent
VK476 Viking 15630MC 4.9 1/2" NPT Residential Flush Pendent
VK494 Viking 20759 4.9 1/2" NPT Residential Concealed Pendent
VK466 Viking 13781 5.2 1/2" NPT Residential Pendent
VK466-D Viking 13781AX 5.2 1/2" NPT Residential Concealed Pendent

Return to the table of contents or contact us with questions.

 

Residential: 5.6K & Over (Grouped by K-Factor and Sorted by SIN)

SIN Manufacturer Part Number K-Factor Thread Description
SS4523 Senju SS4523 5.6 1/2" NPT Residential Flush Horizontal Sidewall
TY3111 Tyco 53-111-1-165 5.6 1/2" NPT Model TY-L Upright
TY3113 Tyco 53-253-1-212 5.6 1/2" NPT TY-L Standard Response Intermediate Level Upright
TY3121 Tyco 58-974-1-165 5.6 1/2" NPT Model TY-FRL Quick Response Upright
TY3132 Tyco 58-986-1-165 5.6 1/2" NPT TY-FRL Quick Response Intermediate Level Upright
TY3211 Tyco 53-112-1-165 5.6 1/2" NPT Model TY-L Pendent
TY3221 Tyco 58-982-1-165 5.6 1/2" NPT Model TY-FRL Quick Response Pendent
TY3311 Tyco 53-113-1-165 5.6 1/2" NPT Model TY-L Horizontal Sidewall
TY3321 Tyco 58-946-1-165 5.6 1/2" NPT Model TY-FRL Quick Response Horizontal Sidewall
TY3334 Tyco 51-524-1-155 5.6 1/2" NPT LFII Horizontal Sidewall
V2744 Victaulic V2744 5.6 1/2" NPT Residential Horizontal Sidewall: Quick Response
V3806 Victaulic V3806 5.6 1/2" NPT Residential Concealed Pendent: Quick Response
SS8561 Senju SS8561 5.8 1/2" NPT Residential Concealed Pendent
TY4334 Tyco 51-534-1-155 5.8 1/2" NPT LFII Horizontal Sidewall
VK460 Viking 13933 5.8 1/2" NPT Residential Horizontal Sidewall
VK472 Viking 16130 5.8 1/2" NPT Residential Pendent
VK474 Viking 15790AC 5.8 1/2" NPT Residential Concealed Pendent
VK490 Viking 20409 5.8 1/2" NPT Freedom Residential Concealed Pendent
TY4234 Tyco 51-069-1-155 6.9 3/4" NPT LFII Pendent Recessed
V2902 Victaulic V2902 6.9 1/2" NPT Residential Pendent: Quick Response
V3426 Victaulic V3426 6.9 3/4" NPT Residential Pendent: Quick Response
VK458 Viking 13230 7.4 3/4" NPT Residential Pendent
VK458-D Viking 13230ABX 7.4 3/4" NPT Residential Domed Concealed Pendent
TY4111 Tyco 53-101-1-165 8.0 3/4" NPT Model TY-L Upright
TY4113 Tyco 53-153-1-212 8.0 3/4" NPT TY-L Standard Response Intermediate Level Upright
TY4121 Tyco 58-174-1-165 8.0 3/4" NPT Model TY-FRL Quick Response Upright
TY4123 Tyco 58-153-1-165 8.0 3/4" NPT TY-FRL Quick Response Intermediate Level Upright
TY4211 Tyco 53-102-1-165 8.0 3/4" NPT Model TY-L Pendent
TY4221 Tyco 58-172-1-165 8.0 3/4" NPT Model TY-FRL Quick Response Pendent
TY4811 Tyco 53-106-1-165 8.0 1/2" NPT Model TY-L Upright
TY4911 Tyco 53-107-1-165 8.0 1/2" NPT Model TY-L Recessed Pendent

Return to the table of contents or contact us with questions.

 

SIN Directory for Dry Fire Sprinklers

Dry: 5.6K

SIN Manufacturer Part Number K-Factor Thread Description
V3301 Victaulic V3301 5.6 1" NPT Dry Concealed Pendent: Standard Response
V3302 Victaulic V3302 5.6 1" NPT Dry Concealed Pendent: Quick Response
V3505 Victaulic V3505 5.6 1" NPT Dry VicFlex Style VS1 Pendent: Standard Response
V3506 Victaulic V3506 5.6 1" NPT Dry VicFlex Style VS1 Pendent: Quick Response
V3509 Victaulic V3509 5.6 1" NPT Dry Style VS1 Horizontal Sidewall: Standard Response
V3510 Victaulic V3510 5.6 1" NPT Dry Style VS1 Horizontal Sidewall: Quick Response
V3517 Victaulic V3517 5.6 1" NPT Dry Style VS1 Concealed Pendent: Standard Response
V3518 Victaulic V3518 5.6 1" NPT Dry Style VS1 Concealed Pendent: Quick Response
V3601 Victaulic V3601 5.6 1" NPT Dry Upright: Standard Response
V3602 Victaulic V3602 5.6 1" NPT Dry Upright: Quick Response
V3605 Victaulic V3605 5.6 1" NPT Dry Pendent: Standard Response
V3606 Victaulic V3606 5.6 1" NPT Dry Pendent: Quick Response
V3609 Victaulic V3609 5.6 1" NPT Dry Horizontal Sidewall: Standard Response
V3610 Victaulic V3610 5.6 1" NPT Dry Horizontal Sidewall: Quick Response
VK150 Viking 07852U 5.6 1" NPT Standard Response Plain Barrel Dry Pendent
VK151 Viking 9343 5.6 1" NPT Plain Barrel Dry Pendent
VK152 Viking 07858U 5.6 1" NPT Standard Response Plain Barrel Dry Horizontal Sidewall
VK153 Viking 09125U 5.6 1" NPT Standard Response Plain Barrel Dry Vertical Sidewall
VK154 Viking 07740U 5.6 1" NPT Standard Response Adjustable Standard Dry Pendent
VK155 Viking 9341 5.6 1" NPT Adjustable Standard Dry Pendent
VK156 Viking 07857U 5.6 1" NPT Standard Response Adjustable Standard Dry Horizontal Sidewall
VK157 Viking 09123U 5.6 1" NPT Standard Response Adjustable Standard Dry Vertical Sidewall
VK158 Viking 06530U 5.6 1" NPT Standard Response Adjustable Recessed Dry Pendent
VK159 Viking 9342 5.6 1" NPT Adjustable Recessed Dry Pendent
VK160 Viking 8050 5.6 1" NPT Standard Response Plain Barrel Dry Upright
VK161 Viking 09124U 5.6 1" NPT Standard Response Adjustable Recessed Dry Vertical Sidewall
VK162 Viking 07856U 5.6 1" NPT Standard Response Adjustable Recessed Dry Horizontal Sidewall
VK168 Viking 09798U 5.6 1" NPT Standard Response Stainless Steel Plain Barrel Dry Pendent
VK169 Viking 10360U 5.6 1" NPT Standard Response Stainless Steel Adjustable Recessed Dry Pendent
VK172 Viking 08387U 5.6 1" NPT Quick Response Plain Barrel Dry Pendent
VK174 Viking 08388U 5.6 1" NPT Quick Response Plain Barrel Dry HSW
VK176 Viking 08383U 5.6 1" NPT Quick Response Adjustable Standard Dry Pendent
VK178 Viking 08384U 5.6 1" NPT Quick Response Adjustable Standard Dry Horizontal Sidewall
VK180 Viking 08385U 5.6 1" NPT Quick Response Adjustable Recessed Dry Pendent
VK182 Viking 08386U 5.6 1" NPT Quick Response Adjustable Recessed Dry Horizontal Sidewall
VK184 Viking 08417UA 5.6 1" NPT Quick Response Dry Upright
VK188 Viking 10542U 5.6 1" NPT Standard Response/Quick Response Extended Coverage Adjustable Recessed Dry Horizontal Sidewall
VK190-D Viking 12421UA 5.6 1" NPT Standard Response Dry Domed Concealed Pendent
VK194-D Viking 12422UA 5.6 1" NPT Quick Response Dry Domed Concealed Pendent
VK196-D Viking 12423UA 5.6 1" NPT Standard/QR EC Dry Domed Concealed Pendent
VK482 Viking 18385 5.6 1" NPT Quick Response Flush Concealed Dry Pendent

Return to the table of contents or contact us with questions.

 

Dry 8.0K & 11.2K (Sorted by Sprinkler Identification Number)

SIN Manufacturer Part Number K-Factor Thread Description
V3303 Victaulic V3303 8.0 1" NPT Dry Concealed Pendent: Standard Response
V3304 Victaulic V3304 8.0 1" NPT Dry Concealed Pendent: Quick Response
V3603 Victaulic V3603 8.0 1" NPT Dry Upright: Standard Response
V3604 Victaulic V3604 8.0 1" NPT Dry Upright: Quick Response
V3607 Victaulic V3607 8.0 1" NPT Dry Pendent: Standard Response
V3608 Victaulic V3608 8.0 1" NPT Dry Pendent: Quick Response
V3611 Victaulic V3611 8.0 1" NPT Dry Horizontal Sidewall: Standard Response
V3612 Victaulic V3612 8.0 1" NPT Dry Horizontal Sidewall: Quick Response
VK163 Viking 12810U 8.0 1" NPT Standard Response Adjustable Standard Dry Pendent
VK164 Viking 12811U 8.0 1" NPT Standard Response Adjustable Recessed Dry Pendent
VK166 Viking 12741U 8.0 1" NPT Standard Response Plain Barrel Dry Pendent
VK173 Viking 13248U 8.0 1" NPT Quick Response Ordinary Hazard Plain Barrel Dry Pendent
VK177 Viking 13249U 8.0 1" NPT Quick Response Ordinary Hazard Adjustable Standard Dry Pendent
VK181 Viking 13250U 8.0 1" NPT Quick Response Ordinary Hazard Adjustable Recessed Dry Pendent
VK192-D Viking 12424UA 8.0 1" NPT Standard Response Dry Domed Concealed Pendent
VK250 Viking 13173U 8.0 1" NPT Standard Response Ordinary Hazard Plain Barrel Dry HSW
VK252 Viking 13172U 8.0 1" NPT Standard Response Ordinary Hazard Adjustable Standard Dry HSW
VK254 Viking 13174U 8.0 1" NPT Standard Response Ordinary Hazard Adjustable Recessed Dry HSW
VK275 Viking 13170U 8.0 1" NPT Quick Response Ordinary Hazard Plain Barrel Dry HSW
VK277 Viking 13169U 8.0 1" NPT Quick Response Ordinary Hazard Adjustable Standard Dry HSW
VK2773 Viking 21489U 8.0 1" NPT Quick Response Ordinary Hazard Adjustable Standard Dry HSW
VK279 Viking 13171U 8.0 1" NPT Quick Response Ordinary Hazard Adjustable Recessed Dry HSW
VK282 Viking 13254U 8.0 1" NPT Quick Response Plain Barrel Dry Pendent Fusible Link
VK284 Viking 13239U 8.0 1" NPT Quick Response Ordinary Hazard Plain Barrel Dry HSW Fusible Link
VK286 Viking 13255U 8.0 1" NPT Quick Response Adjustable Standard Dry Pendent Fusible Link
VK288 Viking 13240U 8.0 1" NPT Quick Response Ordinary Hazard Adjustable Standard Dry HSW Fusible Link
VK290 Viking 13256U 8.0 1" NPT Quick Response Adjustable Recessed Dry Pendent Fusible Link
VK292 Viking 13241U 8.0 1" NPT Quick Response Ordinary Hazard Adjustable Recessed Dry HSW Fusible Link
VK544 Viking 19830, 19831 11.2 1-1/4" NPT Standard Response Dry Pendent ELO
VK545 Viking 19835, 19836 11.2 1-1/4" NPT Standard Response Dry Pendent ELO
VK546 Viking 19840, 19841 11.2 1-1/4" NPT Standard Response Dry Pendent ELO
VK547 Viking 19828, 19829 11.2 1-1/4" NPT Quick Response Dry Pendent ELO
VK548 Viking 19833, 19834 11.2 1-1/4" NPT Quick Response Dry Pendent ELO
VK549 Viking 19838, 19839 11.2 1-1/4" NPT Quick Response Dry Pendent ELO

Return to the table of contents or contact us with questions.

 

SIN Directory for Storage, Institutional, ELO, Extended Coverage, and Other Sprinkler Types

Storage (Grouped by K-Factor, Sorted by Sprinkler Identification Number)

SIN Manufacturer Part Number K-Factor Thread Description
V2721 Victaulic V2721 5.6 1/2" NPT Storage Upright: Standard Response
V2722 Victaulic V2722 5.6 1/2" NPT Storage Upright: Quick Response
V2723 Victaulic V2723 5.6 1/2" NPT Storage Pendent: Standard Response
V2724 Victaulic V2724 5.6 1/2" NPT Storage Pendent: Quick Response
VK550 Viking 10138U, 12986U 5.6 1/2" NPT Standard Response Upright Intermediate Level
VK551 Viking 12279U 5.6 1/2" NPT Quick Response Fusible Element Upright Intermediate Level
VK552 Viking 05557U, 12973U 5.6 1/2" NPT Standard Response Fusible Link Upright Intermediate Level
VK556 Viking 06661BU, 12978U 5.6 1/2" NPT Quick Response Upright Intermediate Level
V3417 Victaulic V3417 8.0 3/4" NPT Storage Upright: Standard Response
V3418 Victaulic V3418 8.0 3/4" NPT Storage Upright: Quick Response
V3419 Victaulic V3419 8.0 3/4" NPT Storage Pendent: Standard Response
V3420 Victaulic V3420 8.0 3/4" NPT Storage Pendent: Quick Response
VK560 Viking 10141U 8 3/4" NPT Standard Response Upright Intermediate Level
VK562 Viking 05514U 8 3/4" NPT Standard Response Fusible Link Upright Intermediate Level
VK566 Viking 06665BU 8 3/4" NPT Quick Response Upright Intermediate Level
VK567 Viking 13976U 8 3/4" NPT Quick Response Upright Intermediate Level
V3403 Victaulic V3403 11.2 3/4" NPT Storage Upright: Standard Response
V3404 Victaulic V3404 11.2 3/4" NPT Storage Upright: Quick Response
V3407 Victaulic V3407 11.2 3/4" NPT Storage Pendent: Standard Response
V3408 Victaulic V3408 11.2 3/4" NPT Storage Pendent: Quick Response
V4702 Victaulic V4702 16.8 3/4" NPT Storage ESFR Pendent: ESFR
V4601 Victaulic V4601 25.2 1" NPT Storage CMSA Pendent: Standard Response
V4603 Victaulic V4603 25.2 1" NPT Storage CMSA Upright: Standard Response

Return to the table of contents or contact us with questions.

 

Institutional

SIN Manufacturer Part Number K-Factor Thread Description
TY1281 Tyco 50-310-4-165 5.6 1/2" NPT RAVEN Studio Pendent Quick Response Standard Coverage
TY1282 Tyco 50-312-4-165 5.6 1/2" NPT RAVEN Studio Horizontal Sidewall Quick Response Standard Coverage
TY3281 Tyco 50-314-9-165 5.6 1/2" NPT Raven Institutional Pendent Standard Coverage
TY3290 Tyco 51-104-9-165 5.6 1/2" NPT TFP PH2 Institutional Pendent
TY3381 Tyco 50-316-9-165 5.6 1/2" NPT Raven Institutional Horizontal Sidewall Standard Coverage
TY3390 Tyco 51-106-9-165 5.6 1/2" NPT TFP PH5 Institutional Horizontal Sidewall
VK412 Viking 10579 5.6 1/2" NPT Quick Response Model HQR-2 Fusible Link Flush Horizontal Sidewall

Return to the table of contents or contact us with questions.

 

Extra Large Orifice (ELO)

SIN Manufacturer Part Number K-Factor Thread Description
VK375 Viking 8338 11.2 3/4" NPT Quick Response ELO Upright, Extra-Large Orifice
VK377 Viking 08337, 17489 11.2 3/4" NPT Quick Response ELO Pendent, (Special Application)
VK469 Viking 15764A 11.2 3/4" NPT Quick Response ELO Concealed Pendent, Extra Large Orifice
VK530 Viking 9679 11.2 3/4" NPT Standard Response ELO Upright (Special Application)
VK531 Viking 10633 11.2 3/4" NPT Quick Response ELO Upright (Special Application)
VK5311 Viking 19304, 19305 11.2 3/4" NPT Quick Response ELO Upright (Special Application)
VK532 Viking 8687 11.2 3/4" NPT Standard/Quick Response EC LH/OH ELO Upright
VK533 Viking 13978 11.2 3/4" NPT Quick Response ELO Fusible Element Upright (Special Application)
VK534 Viking 8340 11.2 3/4" NPT Standard and QR ECOH ELO Pendent
VK535 Viking 14139 11.2 3/4" NPT Standard and QR ECOH ELO Fusible Element Upright
VK536 Viking 7961 11.2 3/4" NPT Standard Response ELO Upr (Special Application) and Pdt
VK537 Viking 14611 11.2 3/4" NPT Standard and QR ECOH ELO Fusible Element Pendent

Return to the table of contents or contact us with questions.

 

Extended Coverage (EC, QREC)

SIN Manufacturer Part Number K-Factor Thread Description
SS3521 Senju SS3521 5.6 1/2" NPT Flush Pendent: QREC (Quick Response Extended Coverage)
SS3561 Senju SS3561 5.6 1/2" NPT Concealed Pendent: QREC (Quick Response Extended Coverage)
TY1381 Tyco 50-311-4-165 5.6 1/2" NPT RAVEN Studio Pendent Quick Response Extended Coverage
TY1382 Tyco 50-318-4-165 5.6 1/2" NPT RAVEN Studio Horizontal Sidewall Quick Response Extended Coverage
TY3232 Tyco 51-051-1-135 5.6 1/2" NPT EC-5 Quick Response Recessed Pendent
TY3282 Tyco 50-315-9-165 5.6 1/2" NPT Raven Institutional Pendent Extended Coverage
TY3302 Tyco 51-053-1-135 5.6 1/2" NPT EC-5 Quick Response Horizontal Sidewall
TY3322 Tyco 58-970-1-165 5.6 1/2" NPT TY-FRL Extended Coverage Quick Response Horizontal Sidewall
TY3382 Tyco 50-317-9-165 5.6 1/2" NPT Raven Institutional Horizontal Sidewall Extended Coverage
TY3532 Tyco 51-794-1-155 5.6 1/2" NPT RFII Pendent Concealed Extended Coverage
VK600 Viking 06778B 5.6 1/2" NPT Standard Response/Quick Response Extended Coverage Pendent
VK601 Viking 13969 5.6 1/2" NPT Quick Response EC Fusible Element Pendent
VK604 Viking 10335 5.6 1/2" NPT Standard Response/Quick Response -5 Extended Coverage Pendent
VK605 Viking 12120 5.6 1/2" NPT -5 Horizontal Sidewall (with EC, QREC, and Specific Application Listings)
VK607 Viking 13970 5.6 1/2" NPT Standard Response/Quick Response Extended Coverage Fusible Element Pendent
VK609 Viking 13971 5.6 1/2" NPT Standard Response/Quick Response Extended Coverage Fusible Element Horizontal Sidewall
VK610 Viking 12294 5.6 1/2" NPT HP Standard Response/Quick Response -5 Extended Coverage Pendent
VK611 Viking 13972 5.6 1/2" NPT HP Standard Response/Quick Response Extended Coverage Fusible Element Pendent
VK612 Viking 12295 5.6 1/2" NPT HP Standard Response/Quick Response -5 EC Horizontal Sidewall
VK613 Viking 13973 5.6 1/2" NPT HP Standard Response/Quick Response Extended Coverage Fusible Element Horizontal Sidewall
VK614-D Viking 06778BAX 5.6 1/2" NPT Standard Response/Quick Response Extended Coverage Domed Concealed Pendent
VK632 Viking 14613A 5.6 1/2" NPT Quick Response EC Concealed Pendent
TY4232 Tyco 50-801-1-135 8.0 3/4" NPT EC-8 Quick Response Recessed Pendent
TY4322 Tyco 58-170-1-165 8.0 3/4" NPT TY-FRL Quick Response Extended Coverage Horizontal Sidewall
TY4332 Tyco 51-396-1-155 8.0 3/4" NPT CHEC Concealed Horizontal Sidewall Extended Coverage
V3102 Victaulic V3102 8.0 3/4" NPT Extended Coverage Concealed Pendent: Quick Response
V3415 Victaulic V3415 8.0 3/4" NPT Extended Coverage Horizontal Sidewall: Standard Response
V3416 Victaulic V3416 8.0 3/4" NPT Extended Coverage Horizontal Sidewall: Quick Response
V3428 Victaulic V3428 8.0 3/4" NPT Extended Coverage Pendent: Quick Response
VK602 Viking 07077B, 18262 8.0 3/4" NPT Standard Response/Quick Response Extended Coverage Pendent
VK603 Viking 14140, 18277 8.0 3/4" NPT Quick Response Extended Coverage Pendent
VK606 Viking 13005, 18271 8.0 3/4" NPT Standard Response/Quick Response Extended Coverage Horizontal Sidewall
VK630 Viking 13500 8.0 3/4" NPT Quick Response Extended Coverage Horizontal Sidewall
VK630-D Viking 13500AX 8.0 3/4" NPT Quick Response EC Domed Concealed Horizontal Sidewall
VK634 Viking 14535A 8.0 3/4" NPT Quick Response EC Concealed Pendent
VK638 Viking 17375 8.0 3/4" NPT Quick Response EC Horizontal Sidewall
VK680 Viking 17114AC 8.0 3/4" NPT Quick Response EC Concealed Horizontal Sidewall
V3104 Victaulic V3104 11.2 3/4" NPT Extended Coverage Concealed Pendent: Quick Response
V3411 Victaulic V3411 11.2 3/4" NPT Extended Coverage Pendent: Standard Response
V3412 Victaulic V3412 11.2 3/4" NPT Extended Coverage Pendent: Quick Response
VK538 Viking 17115A 11.2 3/4" NPT EC/QREC OH Concealed Pendent, Extra-Large Orifice
VK608 Viking 8339 11.2 3/4" NPT Standard Response/Quick Response Extended Coverage Light Hazard Extra-Large Orifice Pendent
VK617 Viking 14141 11.2 3/4" NPT Standard Response/Quick Response Extended Coverage Light Hazard Extra-Large Orifice Fusible Element Pendent
VK618-D Viking 08339AX 11.2 3/4" NPT Standard Response/Quick Response Extended Coverage Domed Concealed Light Hazard Extra-Large Orifice Pendent
VK636 Viking 16102A 11.2 3/4" NPT Quick Response EC LH Concealed Pendent, Extra-Large Orifice
V3413 Victaulic V3413 14.0 3/4" NPT Extended Coverage Pendent: Standard Response
V3414 Victaulic V3414 14.0 3/4" NPT Extended Coverage Pendent: Quick Response
V3421 Victaulic V3421 14.0 3/4" NPT Extended Coverage Pendent: Standard Response
V3425 Victaulic V3425 14.0 3/4" NPT Extended Coverage Upright: Standard Response
VK570 Viking 13840 14 3/4" NPT Extended Coverage Ordinary Hazard Upright
VK572 Viking 13722 14 3/4" NPT Extended Coverage Ordinary Hazard Pendent
VK595 Viking 16859 25.2 1" NPT EC Upright (Storage-Density/Area)

Return to the table of contents or contact us with questions.

 

Spray/Foam Nozzles

SIN Manufacturer Part Number K-Factor Thread Description
V1201-V1278 Victaulic Various 1.2 1/2" NPT Nozzle/Open Spray Nozzle: Open
VK740 Viking 05133AAJ or AJJ 1.2 1/2" NPT 30-Degree Model A-2 Spray Nozzle
VK741 Viking 05133AAK or AJK 1.2 1/2" NPT 60-Degree Model A-2 Spray Nozzle
VK742 Viking 05133AAL or AJL 1.2 1/2" NPT 90-Degree Model A-2 Spray Nozzle
VK743 Viking 05133AAM or AJM 1.4 1/2" NPT 120-Degree Model A-2 Spray Nozzle
VK744 Viking 05133AAN or AJN 1.4 1/2" NPT 140-Degree Model A-2 Spray Nozzle
VK750 Viking 05134AAJ or AJJ 2 1/2" NPT 30-Degree Model A-2X Spray Nozzle
VK751 Viking 05134AAK or AJK 2 1/2" NPT 60-Degree Model A-2X Spray Nozzle
VK752 Viking 05134AAL or AJL 2 1/2" NPT 90-Degree Model A-2X Spray Nozzle
VK753 Viking 05134AAM or AJM 2.2 1/2" NPT 120-Degree Model A-2X Spray Nozzle
VK754 Viking 05134AAN or AJN 2.2 1/2" NPT 140-Degree Model A-2X Spray Nozzle
V2601 Victaulic V2601 2.8 1/2" NPT Nozzle/Foam Nozzle: Open
VK760 Viking 05135AAJ or AJJ 2.8 1/2" NPT 30-Degree Model B-2 Spray Nozzle
VK761 Viking 05135AAK or AJK 2.8 1/2" NPT 60-Degree Model B-2 Spray Nozzle
VK762 Viking 05135AAL or AJL 2.8 1/2" NPT 90-Degree Model B-2 Spray Nozzle
VK763 Viking 05135AAM or AJM 3.3 1/2" NPT 120-Degree Model B-2 Spray Nozzle
VK764 Viking 05135AAN or AJN 3.3 1/2" NPT 140-Degree Model B-2 Spray Nozzle
VK770 Viking 05136AAJ or AJJ 3.4 1/2" NPT 30-Degree Model C-2 Spray Nozzle
VK771 Viking 05136AAK or AJK 3.4 1/2" NPT 60-Degree Model C-2 Spray Nozzle
VK772 Viking 05136AAL or AJL 3.8 1/2" NPT 90-Degree Model C-2 Spray Nozzle
VK773 Viking 05136AAM or AJM 3.9 1/2" NPT 120-Degree Model C-2 Spray Nozzle
VK774 Viking 05136AAN or AJN 3.9 1/2" NPT 140-Degree Model C-2 Spray Nozzle
VK780 Viking 05137AAJ or AJJ 4.7 1/2" NPT 30-Degree Model D-2 Spray Nozzle
VK781 Viking 05137AAK or AJK 4.7 1/2" NPT 60-Degree Model D-2 Spray Nozzle
VK782 Viking 05137AAL or AJL 5 1/2" NPT 90-Degree Model D-2 Spray Nozzle
VK783 Viking 05137AAM or AJM 5.2 1/2" NPT 120-Degree Model D-2 Spray Nozzle
VK784 Viking 05137AAN or AJN 5.2 1/2" NPT 140-Degree Model D-2 Spray Nozzle
V2603 Victaulic V2603 5.6 1/2" NPT Nozzle/Foam Nozzle: Open
VK920 Viking 15111 (Discontinued) 5.6 1/2" NPT Flat Spray QR Pendent Sprinkler
VK810 Viking 12867 7.2 1/2" NPT 65-Degree Model E Spray Nozzle
VK811 Viking 12874 7.2 1/2" NPT 80-Degree Model E Spray Nozzle
VK812 Viking 12881 7.2 1/2" NPT 95-Degree Model E Spray Nozzle
VK813 Viking 12888 7.2 1/2" NPT 110-Degree Model E Spray Nozzle
VK814 Viking 12895 7.2 1/2" NPT 125-Degree Model E Spray Nozzle
VK815 Viking 12902 7.2 1/2" NPT 140-Degree Model E Spray Nozzle
VK816 Viking 12909 7.2 1/2" NPT 160-Degree Model E Spray Nozzle
VK817 Viking 12916 7.2 1/2" NPT 180-Degree Model E Spray Nozzle
VK922 Viking 15112 (Discontinued) 8.0 3/4" NPT Flat Spray QR Pendent Sprinkler

Return to the table of contents or contact us with questions.

 

Window

SIN Manufacturer Part Number K-Factor Thread Description
V1001 Victaulic V1001 1.4 1/2" NPT Nozzle/Window Sprinkler: Open
V1003 Victaulic V1003 2.0 1/2" NPT Nozzle/Window Sprinkler: Open
VK791 Viking 01321B 2.1 1/2" NPT Model C-1 Window Sprinkler, 5/16" Orifice
V1005 Victaulic V1005 2.8 1/2" NPT Nozzle/Window Sprinkler: Open
V1007 Victaulic V1007 4.2 1/2" NPT Nozzle/Window Sprinkler: Open
VK793 Viking 01323B 4.3 1/2" NPT Model C-1 Window Sprinkler, 7/16" Orifice
TY3388 Tyco 50-305-1-155 5.6 1/2" NPT WS Window Horizontal Sidewall
TY3488 Tyco 50-304-1-155 5.6 1/2" NPT WS Window Vertical Sidewall
V1009 Victaulic V1009 5.6 1/2" NPT Nozzle/Window Sprinkler: Open
VK795 Viking 01325B 7.3 3/4" NPT Model C-1 Window Sprinkler, 5/8" Orifice
V1011 Victaulic V1011 8.0 1/2" NPT Nozzle/Window Sprinkler: Open
V1013 Victaulic V1013 11.5 1/2" NPT Nozzle/Window Sprinkler: Open

Return to the table of contents or contact us with questions.

 

Attic

SIN Manufacturer Part Number K-Factor Thread Description
TY2180 Tyco 50-620-1-200 4.2 1/2" NPT ATTIC BB1 4/12 Pitch 7/12
TY2182 Tyco 50-621-1-200 4.2 1/2" NPT ATTIC BB2 7/12 Pitch 10/12
VK696 Viking 19538 4.2 1/2" NPT Attic Upright Specific Application Attic Sprinkler
TY3180 Tyco 50-601-1-212 5.6 1/2" NPT ATTIC BB1 4/12 Pitch 7/12
TY3181 Tyco 50-602-1-212 5.6 1/2" NPT ATTIC BB2 7/12 Pitch 10/12
TY3182 Tyco 50-603-1-212 5.6 1/2" NPT ATTIC BB3 10/12 Pitch 12/12
TY3183 Tyco 50-611-1-212 5.6 1/2" NPT ATTIC SD1 4/12 Pitch 7/12
TY3184 Tyco 50-612-1-212 5.6 1/2" NPT ATTIC SD2 7/12 Pitch 10/12
TY3185 Tyco 50-613-1-212 5.6 1/2" NPT ATTIC SD3 10/12 Pitch 12/12
TY3187 Tyco 51-620-1-200 5.6 1/2" NPT ATTIC HIP 4/12 Pitch 12/12
TY3190 Tyco 50-625-1-200 5.6 1/2" NPT Attic AP (Attic Plus) 3/12 Pitch 12/12
VK684 Viking 19627 5.6 1/2" NPT V-BB Specific Application Attic Sprinkler
VK685 Viking 19801 5.6 1/2" NPT V-BB Specific Application Attic Sprinkler
VK686 Viking 19754 5.6 1/2" NPT V-BB Specific Application Attic Sprinkler
VK693 Viking 19578 5.6 1/2" NPT V-SD Specific Application Attic Sprinkler
VK694 Viking 19799 5.6 1/2" NPT V-SD Specific Application Attic Sprinkler
VK695 Viking 19759 5.6 1/2" NPT V-SD Specific Application Attic Sprinkler
VK697 Viking 21716 5.6 1/2" NPT Attic Upright Specific Application Attic Sprinkler
TY4180 Tyco 51-623-1-200 8.0 3/4" NPT ATTIC BB1 4/12 Pitch 7/12
TY4181 Tyco 51-621-1-200 8.0 3/4" NPT ATTIC BB2 7/12 Pitch 10/12
TY4182 Tyco 51-622-1-200 8.0 3/4" NPT ATTIC BB3 10/12 Pitch 12/12
VK681 Viking 19626 8.0 3/4" NPT V-BB Specific Application Attic Sprinkler
VK682 Viking 19798 8.0 3/4" NPT V-BB Specific Application Attic Sprinkler
VK683 Viking 19751 8.0 3/4" NPT V-BB Specific Application Attic Sprinkler

Return to the table of contents or contact us with questions.

 

Sprinklers for High-Challenge Fires

SIN Manufacturer Part Number K-Factor Thread Description
V2502 Victaulic V2502 8.0 1/2" NPT Specific Application Upright: Quick Response
VK514 Viking 19591, 19592 8.0 1" NPT Specific Application ESFR Pendent
VK580 Viking 12739 8.0 3/4" NPT Standard Response Upright
VK598 Viking 19522A, 19764A 8.0 1" NPT Standard Response Upright

Return to the table of contents or contact us with questions.

 

Uncategorized (Conventional, High-Pressure, and More)

SIN Manufacturer Part Number K-Factor Thread Description
TY1189 Tyco 50-300-1-175 8.0 1/2" NPT CC1 Combustible Concealed Upright
TY2189 Tyco 51-311-1-175 8.0 1/2" NPT CC2 Combustible Concealed Space Upright
TY2199 Tyco 51-311-1-200 8.0 1/2" NPT CC3 Combustible Concealed Space Upright
TY3189 Tyco 51-301-1-175 8.0 1/2" NPT CC2 Combustible Concealed Space Upright
VK375 Viking 8338 8.0 3/4" NPT Quick Response ELO Upright, Extra-Large Orifice
VK377 Viking 08337, 17489 8.0 3/4" NPT Quick Response ELO Pendent, (Special Application)
VK469 Viking 15764A 8.0 3/4" NPT Quick Response ELO Concealed Pendent, Extra Large Orifice
VK530 Viking 9679 8.0 3/4" NPT Standard Response ELO Upright (Special Application)
VK531 Viking 10633 8.0 3/4" NPT Quick Response ELO Upright (Special Application)
VK5311 Viking 19304, 19305 8.0 3/4" NPT Quick Response ELO Upright (Special Application)
VK532 Viking 8687 8.0 3/4" NPT Standard/Quick Response EC LH/OH ELO Upright
VK533 Viking 13978 8.0 3/4" NPT Quick Response ELO Fusible Element Upright (Special Application)
VK534 Viking 8340 8.0 3/4" NPT Standard and QR ECOH ELO Pendent
VK535 Viking 14139 8.0 3/4" NPT Standard and QR ECOH ELO Fusible Element Upright
VK536 Viking 7961 8.0 3/4" NPT Standard Response ELO Upr (Special Application) and Pdt
VK537 Viking 14611 8.0 3/4" NPT Standard and QR ECOH ELO Fusible Element Pendent
SS3521 Senju SS3521 8.0 1/2" NPT Flush Pendent: QREC (Quick Response Extended Coverage)
SS3561 Senju SS3561 8.0 1/2" NPT Concealed Pendent: QREC (Quick Response Extended Coverage)
TY1381 Tyco 50-311-4-165 8.0 1/2" NPT RAVEN Studio Pendent Quick Response Extended Coverage
TY1382 Tyco 50-318-4-165 8.0 1/2" NPT RAVEN Studio Horizontal Sidewall Quick Response Extended Coverage
TY3232 Tyco 51-051-1-135 8.0 1/2" NPT EC-5 Quick Response Recessed Pendent
TY3282 Tyco 50-315-9-165 8.0 1/2" NPT Raven Institutional Pendent Extended Coverage
TY3302 Tyco 51-053-1-135 8.0 1/2" NPT EC-5 Quick Response Horizontal Sidewall
TY3322 Tyco 58-970-1-165 8.0 1/2" NPT TY-FRL Extended Coverage Quick Response Horizontal Sidewall
TY3382 Tyco 50-317-9-165 8.0 1/2" NPT Raven Institutional Horizontal Sidewall Extended Coverage
TY3532 Tyco 51-794-1-155 8.0 1/2" NPT RFII Pendent Concealed Extended Coverage
VK600 Viking 06778B 8.0 1/2" NPT Standard Response/Quick Response Extended Coverage Pendent
VK601 Viking 13969 8.0 1/2" NPT Quick Response EC Fusible Element Pendent
VK604 Viking 10335 8.0 1/2" NPT Standard Response/Quick Response -5 Extended Coverage Pendent
VK605 Viking 12120 8.0 1/2" NPT -5 Horizontal Sidewall (with EC, QREC, and Specific Application Listings)
VK607 Viking 13970 8.0 1/2" NPT Standard Response/Quick Response Extended Coverage Fusible Element Pendent
VK609 Viking 13971 8.0 1/2" NPT Standard Response/Quick Response Extended Coverage Fusible Element Horizontal Sidewall
VK610 Viking 12294 8.0 1/2" NPT HP Standard Response/Quick Response -5 Extended Coverage Pendent
VK611 Viking 13972 8.0 1/2" NPT HP Standard Response/Quick Response Extended Coverage Fusible Element Pendent
VK612 Viking 12295 8.0 1/2" NPT HP Standard Response/Quick Response -5 EC Horizontal Sidewall
VK613 Viking 13973 8.0 1/2" NPT HP Standard Response/Quick Response Extended Coverage Fusible Element Horizontal Sidewall
VK614-D Viking 06778BAX 8.0 1/2" NPT Standard Response/Quick Response Extended Coverage Domed Concealed Pendent
VK632 Viking 14613A 8.0 1/2" NPT Quick Response EC Concealed Pendent
TY4232 Tyco 50-801-1-135 8.0 3/4" NPT EC-8 Quick Response Recessed Pendent
TY4322 Tyco 58-170-1-165 8.0 3/4" NPT TY-FRL Quick Response Extended Coverage Horizontal Sidewall
TY4332 Tyco 51-396-1-155 8.0 3/4" NPT CHEC Concealed Horizontal Sidewall Extended Coverage
V3102 Victaulic V3102 8.0 3/4" NPT Extended Coverage Concealed Pendent: Quick Response
V3415 Victaulic V3415 8.0 3/4" NPT Extended Coverage Horizontal Sidewall: Standard Response
V3416 Victaulic V3416 8.0 3/4" NPT Extended Coverage Horizontal Sidewall: Quick Response
V3428 Victaulic V3428 8.0 3/4" NPT Extended Coverage Pendent: Quick Response
VK602 Viking 07077B, 18262 8.0 3/4" NPT Standard Response/Quick Response Extended Coverage Pendent
VK603 Viking 14140, 18277 8.0 3/4" NPT Quick Response Extended Coverage Pendent
VK606 Viking 13005, 18271 8.0 3/4" NPT Standard Response/Quick Response Extended Coverage Horizontal Sidewall
VK630 Viking 13500 8.0 3/4" NPT Quick Response Extended Coverage Horizontal Sidewall
VK630-D Viking 13500AX 8.0 3/4" NPT Quick Response EC Domed Concealed Horizontal Sidewall
VK634 Viking 14535A 8.0 3/4" NPT Quick Response EC Concealed Pendent
VK638 Viking 17375 8.0 3/4" NPT Quick Response EC Horizontal Sidewall
VK680 Viking 17114AC 8.0 3/4" NPT Quick Response EC Concealed Horizontal Sidewall
V3104 Victaulic V3104 8.0 3/4" NPT Extended Coverage Concealed Pendent: Quick Response
V3411 Victaulic V3411 8.0 3/4" NPT Extended Coverage Pendent: Standard Response
V3412 Victaulic V3412 8.0 3/4" NPT Extended Coverage Pendent: Quick Response
VK538 Viking 17115A 8.0 3/4" NPT EC/QREC OH Concealed Pendent, Extra-Large Orifice
VK608 Viking 8339 8.0 3/4" NPT Standard Response/Quick Response Extended Coverage Light Hazard Extra-Large Orifice Pendent
VK617 Viking 14141 8.0 3/4" NPT Standard Response/Quick Response Extended Coverage Light Hazard Extra-Large Orifice Fusible Element Pendent
VK618-D Viking 08339AX 8.0 3/4" NPT Standard Response/Quick Response Extended Coverage Domed Concealed Light Hazard Extra-Large Orifice Pendent
VK636 Viking 16102A 8.0 3/4" NPT Quick Response EC LH Concealed Pendent, Extra-Large Orifice
V3413 Victaulic V3413 8.0 3/4" NPT Extended Coverage Pendent: Standard Response
V3414 Victaulic V3414 8.0 3/4" NPT Extended Coverage Pendent: Quick Response
V3421 Victaulic V3421 8.0 3/4" NPT Extended Coverage Pendent: Standard Response
V3425 Victaulic V3425 8.0 3/4" NPT Extended Coverage Upright: Standard Response
VK570 Viking 13840 8.0 3/4" NPT Extended Coverage Ordinary Hazard Upright
VK572 Viking 13722 8.0 3/4" NPT Extended Coverage Ordinary Hazard Pendent
VK595 Viking 16859 8.0 1" NPT EC Upright (Storage-Density/Area)
V2502 Victaulic V2502 8.0 1/2" NPT Specific Application Upright: Quick Response
VK514 Viking 19591, 19592 8.0 1" NPT Specific Application ESFR Pendent
VK580 Viking 12739 8.0 3/4" NPT Standard Response Upright
VK598 Viking 19522A, 19764A 8.0 1" NPT Standard Response Upright
TY1281 Tyco 50-310-4-165 8.0 1/2" NPT RAVEN Studio Pendent Quick Response Standard Coverage
TY1282 Tyco 50-312-4-165 8.0 1/2" NPT RAVEN Studio Horizontal Sidewall Quick Response Standard Coverage
TY3281 Tyco 50-314-9-165 8.0 1/2" NPT Raven Institutional Pendent Standard Coverage
TY3290 Tyco 51-104-9-165 8.0 1/2" NPT TFP PH2 Institutional Pendent
TY3381 Tyco 50-316-9-165 8.0 1/2" NPT Raven Institutional Horizontal Sidewall Standard Coverage
TY3390 Tyco 51-106-9-165 8.0 1/2" NPT TFP PH5 Institutional Horizontal Sidewall
VK412 Viking 10579 8.0 1/2" NPT Quick Response Model HQR-2 Fusible Link Flush Horizontal Sidewall
TY3191 Tyco 51-036-1-400 8.0 1/2" NPT Issue D Quartzoid High Temp Special
TY3199 Tyco 51-301-1-200 8.0 1/2" NPT CC3 Combustible Concealed Space Upright
TY3291 Tyco 51-040-1-400 8.0 1/2" NPT Issue D Quartzoid High Temp Special
TY4191 Tyco 51-136-1-400 8.0 3/4" NPT Issue D Quartzoid High Temp Special Upright
TY4291 Tyco 51-140-1-400 8.0 3/4" NPT Issue D Quartzoid High Temp Special Pendent
VK015 Viking 9997 8.0 1/2" NPT HP Standard Response Horizontal Sidewall, Small Orifice
VK021 Viking 9995 8.0 1/2" NPT HP Standard Response HP Upright, Small Orifice
VK023 Viking 9994 8.0 1/2" NPT HP Standard Response HP Pendent, Small Orifice
VK116 Viking 9849 8.0 1/2" NPT HP Standard Response -5 Horizontal Sidewall
VK122 Viking 9992 8.0 1/2" NPT HP Standard Response HP Pendent
VK124 Viking 9993 8.0 1/2" NPT HP Standard Response HP Upright
VK310 Viking 06766B, 19391 8.0 1/2" NPT Quick Response Conventional
VK311 Viking 13952, 19392 8.0 1/2" NPT Quick Response Fusible Element Conventional
VK315 Viking 12281 8.0 1/2" NPT HP Quick Response Upright
VK317 Viking 12282 8.0 1/2" NPT HP Quick Response Pendent
VK318 Viking 13954 8.0 1/2" NPT HP Quick Response Fusible Element Pendent
VK319 Viking 12285 8.0 1/2" NPT HP -5 Quick Response Horizontal Sidewall
VK340 Viking 12286 8.0 1/2" NPT HP Quick Response Upright, Small Orifice
VK342 Viking 12290 8.0 1/2" NPT HP Quick Response Pendent, Small Orifice
VK343 Viking 13964 8.0 1/2" NPT HP Quick Response Fusible Element Pendent, Small Orifice
VK344 Viking 12287 8.0 1/2" NPT HP Quick Response Horizontal Sidewall, Small Orifice
VK346 Viking 13965 8.0 1/2" NPT HP Quick Response Fusible Element Horizontal Sidewall, Small Orifice
VK354 Viking 06768B, 18261 8.0 3/4" NPT Quick Response Conventional
VK355 Viking 13979, 18276 8.0 3/4" NPT Quick Response Fusible Element Conventional
VK405 Viking 09782A (Discontinued) 8.0 1/2" NPT HP Standard Response/Quick Response Model B-2 Fusible Link Concealed Pendent
VK454 Viking 12292 (Discontinued) 8.0 1/2" NPT HP Quick Response Model B-2 Fusible Link Concealed Pendent
VK463 Viking 13667A 8.0 1/2" NPT HP Quick Response Concealed Pendent
VK500 Viking 10284 8.0 3/4" NPT Model S-1 ESFR Pendent
VK503 Viking 14073 8.0 3/4" NPT ESFR Pendent
VK510 Viking 12080, 19857, 15221 (Discontinued) 8.0 1" NPT ESFR Pendent
VK520 Viking 10625, 19786 8.0 3/4" NPT Model A-4 ESFR Upright
VK540 Viking 13167 8.0 3/4" NPT Model A-2 Standard Response High Challenge Upright Large Drop, ELO
VK558 Viking 12281U 8.0 1/2" NPT HP Quick Response Upright Intermediate Level
VK900 Viking 12493 8.0 1/2" NPT Coin QR Upright (CMSA)
VK901 Viking 12676AE 8.0 1/2" NPT Coin QR Fusible Element Upright (CMSA)
VK950 Viking 20757 8.0 1/2" NPT Coin QR Upright (CMSA)

Return to the table of contents or contact us with questions.