#70 – Fire Sprinkler Head Replacement Cabinet: How to Make a Sprinkler Kit

A spare sprinkler storage cabinet with the right number and type of heads keeps systems compliant — and working

Every NFPA 13-compliant fire sprinkler system requires a stock of spare fire sprinkler heads. Yet understocked fire sprinkler head cabinets are one of the most common fire code violations spotted by inspectors.

In this article, we explain what you need in a fire sprinkler cabinet and where to keep it. We’ll cover the number and types of spare sprinkler heads required, plus wrenches, and go over common labeling and listing requirements.

Already know what you need? Feel free to skip directly to our selection of replacement fire sprinkler heads, wrenches, and fire sprinkler head cabinets.

The number of spare fire sprinklers required varies with the system’s size

At a minimum, your fire sprinkler head replacement cabinet should contain six spare fire sprinkler heads and a fire sprinkler wrench (or wrenches) suitable to the type of sprinklers in use.

Fire code varies from city to city. But most jurisdictions have adopted codes that reference standards from the National Fire Protection Association (NFPA). NFPA 13: Standard for the Installation of Sprinkler Systems stipulates that each fire sprinkler system requires a stock of at least six spare sprinklers (with the exception of dry fire sprinklers, which we’ll explain in the next section).

From the 2022 edition of NFPA 13

16.2.7.1* A supply of at least six spare sprinklers shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced.

Explanatory material: Spare sprinklers of all the types and ratings installed must be available. For a building with a variety of sprinklers, the number of spare sprinklers should be increased above the minimum

In a later section (16.2.7.5), NFPA 13 adds that the stock of spare sprinklers varies with the size of the fire sprinkler system. The table below details these requirements.

Number of Spare Fire Sprinklers Required in NFPA 13 Systems (2022)
Total Number of Sprinklers Installed Spare Heads Required
Under 300 No fewer than 6
300-1000 No fewer than 12
Over 1000 No fewer than 24

 

Fire sprinkler head cabinet
This cabinet holds six sprinklers and a wrench. The system it serves should have fewer than 300 sprinklers.

Exact spares are not required onsite for some dry sprinklers, but a means of restoring the system after activation is required

NFPA carves out one big exception for fire sprinkler cabinets: dry sprinklers.

Dry-type sprinklers are specially designed and installed for use in areas exposed to low temperatures. Used in docks, freezers, and other locations, these sprinklers feature a length of metal pipe called a barrel that extends from the sprinkler to the piping.

Manufacturers provide dry sprinklers with barrels of different lengths. The lengths vary with expected ambient temperatures: as temperatures grow colder, the minimum length of the barrel grows longer. Some manufacturers provide sprinklers with barrels as long as four feet.

Because dry pipe sprinklers’ lengths can vary even in a single sprinkler system, NFPA 13 requires cabinets for dry sprinklers only if they are all the same length.

From the 2022 edition of NFPA 13

16.2.7.4 Where dry sprinklers of different lengths are installed, spare dry sprinklers shall not be required, provided that a means of returning the system to service is furnished.

The NFPA 13 handbook advises that building owners may keep a stock of their longest sprinklers on hand or use non-dry-type sprinklers as temporary replacements when needed.

All replacement sprinkler heads should be stored in a properly placed cabinet

As cited earlier, NFPA 13 section 16.2.7.1 requires that sprinklers remain in a cabinet and that that cabinet stays onsite. That’s because while some facilities employ on-call sprinkler contractors, there is no guarantee that these contractors will have the specific replacement sprinklers your facility requires. Place these cabinets in an accessible location. One good practice involves storing spare keys in a fire department lockbox or in a location where 24-hour staff—security guards, front desk attendants, and so on—can get to them.

Proper placement also involves keeping the cabinet out of places where heat might inadvertently activate the heads.

From the 2022 edition of NFPA 13

16.2.7.3 The sprinklers shall be kept in a cabinet located where the temperature to which they are subjected will at no time exceed the maximum ceiling temperatures specified in Table 7.2.4.1 for each of the sprinklers within the cabinet.

These temperature requirements vary with the temperature rating of the sprinkler and whether it is a glass-bulb or fusible-link model, as described in tables 7.2.4.1 (a) and (b), adapted below.

Maximum Ceiling Temperatures for Glass-Bulb Fire Sprinklers by Rated Activation Temperature (2022 Edition of NFPA 13)
Maximum Ceiling Temperature Sprinkler Activation Temperature
100F (38C) 135F (57C)
120F (49C) 155F (68C)
150F (66C) 175F (79C) or 200F (93C)
225F (107C) 250F-300F (121C-149C)
300F (149C) 325F-375F (163C-191C)
375F (191C) 400F-475F (204C-246C)
475F (246C) 500F-575F (260C-302C)
625F (329C) 650F (343C)
Maximum Ceiling Temperatures for Fusible-Link Fire Sprinklers by Rated Activation Temperature (2022 Edition of NFPA 13)
Maximum Ceiling Temperature Sprinkler Activation Temperature
100F (38C) 135F-170F (57C-77C)
150F (66C) 175F-225F (79C-107C)
225F (107C) 250F-300F (121C-149C)
300F (149C) 325F-375F (163C-191C)
375F (191C) 400F-475F (204C-246C)
475F (246C) 500F-575F (260C-302C)
625F (329C) 650F (343C)

Each fire sprinkler cabinet requires the wrenches needed to add or remove all installed types of sprinklers

Cabinets containing replacement fire sprinklers must include at least one wrench. However, every cabinet ultimately needs enough fire sprinkler wrenches to install and remove every type of sprinkler currently installed.

From the 2022 edition of NFPA 13

16.2.7.6* One sprinkler wrench as specified by the sprinkler manufacturer shall be provided in the cabinet for each type of sprinkler installed to be used for the removal and installation of sprinklers in the system.

NFPA-compliant cabinets include only wrenches specified by the manufacturer. If you have a variety of sprinklers in use—and those sprinklers require different wrenches—your fire sprinkler cabinet will require more than a single wrench. That said, multiple sprinklers from the same manufacturer may be compatible with one specific wrench.

To learn more, read our blog: “Which Fire Sprinkler Wrench Do I Need?

Required wrench for fire sprinkler head cabinet
This Reliable W2 wrench is specifically designed to quickly (and safely) add or remove Reliable fire sprinkler heads.

Each cabinet must contain spare fire sprinkler heads with the right style, temperature rating, and other critical characteristics

NFPA 13 requires that spare sprinklers kept in a cabinet bear a close resemblance to the sprinklers currently installed.

From the 2022 edition of NFPA 13

16.2.7.2 The sprinklers shall correspond to the types and temperature ratings of the sprinklers in the property.

NFPA further details the requirements for replacement sprinklers in NFPA 25: Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems.

From the 2023 edition of NFPA 25

5.4.1 Sprinklers.

5.4.1.2* Where a threaded sprinkler has been removed from a fitting or welded outlet for any reason, the sprinkler shall not be reinstalled.

5.4.1.2.1 Dry sprinklers shall be permitted to be reinstalled when removed in accordance with the manufacturer’s installation and maintenance instructions.

5.4.1.2.2 A sprinkler shall be permitted to be reinstalled where the sprinkler being removed remains attached to the original fitting or welded outlet or can be removed by a grooved connection, provided that care is taken to ensure the sprinkler is not damaged.

5.4.1.2.3 Sprinklers listed for use with a specifically listed fitting shall be permitted to be reinstalled in accordance with the manufacturer’s installation and maintenance instructions.

5.4.1.3* Replacement sprinklers shall have the proper characteristics for the application intended, which include the following:

(1) Style
(2) Orifice size and K-factor
(3) Temperature rating
(4) Coating, if any
(5) Deflector type (e.g., upright, pendent, sidewall)
(6) Design requirements

A.5.4.1.3 To help in the replacement of like sprinklers, unique sprinkler identification numbers (SINs) are provided on all sprinklers manufactured after January 1, 2001. The SIN accounts for differences in K-factor, deflector characteristics, pressure rating, and thermal sensitivity.

Replacement sprinklers don’t need to match exactly. NFPA guidelines don’t, for instance, require the exact same sprinkler, including model and brand. But locating an exact match is the easiest way to ensure the same performance characteristics for the sprinklers you have and the ones you need to purchase.

Fire sprinkler identification numbers can make completing your cabinet simple

Your sprinkler’s sprinkler identification number (SIN) can make this task considerably easier. The SIN is imprinted on sprinklers made since 2001 (and listed in a complete fire sprinkler cabinet, as we’ll describe next), and it identifies the manufacturer and model of a fire sprinkler. When combined with the activation temperature and finish of a sprinkler, a SIN points to an exact match.

Sprinkler Identification Number
The sprinkler identification number (here labeled as “Model”) identifies the manufacturer and model of a fire sprinkler. 

Check out our guide for more info on identifying your sprinklers’ characteristics and sprinkler identification numbers.

Complete fire sprinkler head cabinets contain a list of the sprinkler types currently installed

All fire sprinkler cabinets must contain a full list of the sprinkler types currently installed. The need for and nature of this list is specified in section 16.2.7.7.1* of NFPA 13 and the system maintenance requirements of NFPA 25:

From the 2023 Edition of NFPA 25

5.4.1.6.6 A list of the sprinklers installed in the property shall be posted in the sprinkler cabinet.

5.4.1.6.6.1* The list shall include the following:

(1) Sprinkler identification number (SIN) if equipped; or the manufacturer, model, orifice, deflector type, thermal sensitivity, and pressure rating
(2) General description
(3) Quantity of each type to be contained in the cabinet
(4) Issue or revision date of the list

A.5.4.1.5.6.1 The minimum information in the list contained in the spare sprinkler cabinet should be marked with the following:
(1) General description of the sprinkler, including upright, pendent, residential, ESFR, and so forth
(2) Quantity of sprinklers to be maintained in the spare sprinkler cabinet

The NFPA 24 Annex also provides a helpful visual example of this list:

Sample fire sprinkler cabinet list

The list helps facilities managers or maintenance contractors select an appropriate replacement when a spare is used. It also expedites sprinkler system inspections required in NFPA 25 by allowing the inspector to confirm that the cabinet contains the appropriate number and types of spares.

Stocking and selecting your fire sprinkler cabinet

QRFS carries a wide selection of fire sprinkler heads designed to meet the needs of your NFPA-compliant system. We offer fire sprinkler heads and wrenches from Victaulic, Senju, Tyco, Viking, and Reliable. We also stock durable, 22-gauge steel sprinkler head cabinets to hold three, six, twelve, and even 24 spare fire sprinklers.

Red fire sprinkler head cabinet
This red-enamel, six-head fire sprinkler cabinet is just one of many available at QRFS.

Our selection also includes large cabinets for storing early-suppression fast response (ESFR) fire sprinkler heads with extra large orifices (ELO).

Click here to browse our selection of fire sprinkler cabinets.

When you buy from QRFS, you benefit from our responsive and knowledgeable customer service. We strive to stay up to date on industry best practices and NFPA codes and standards, so we can provide you with the information you need, when you need it.

Questions about sprinkler cabinets? Having trouble choosing one? Call us at +1 (888) 361-6662 or email support@qrfs.com.

This blog was originally posted by Jason Hugo and Anna Hartenbach at blog.qrfs.com on August 17, 2017, and updated on January 11, 2023. Check us out at Facebook.com/QuickResponseFireSupply or on Twitter @QuickResponseFS.

6 thoughts on “#70 – Fire Sprinkler Head Replacement Cabinet: How to Make a Sprinkler Kit”

  1. Would you have or know where i can get a list like a blank one for the box? i got tagged for this and also wondered it is required to have. Thanks

    Reply
    • Bart — A list is required to have by both NFPA 25 (maintenance standard) and NFPA 13 (installation standard), which are likely enforceable based on your local fire codes. We don’t know of a pre-made blank list, but making one yourself is simple. In the Annex, NFPA 25 provides a visual sample under FIGURE A.5.4.1.5.6.1 (And in NFPA 13: Figure A.6.2.9.7.1). It’s a simple table: the column headings are Sprinkler Identification Number, Sprinkler Temperature Rating, and Sprinkler Quantity Maintained (in the cabinet). The rows are the different types of sprinklers you need in the cabinet.

      Reply
  2. Question: In NFPA 25 there are two requirements for when a sprinkler head must be changed for standard response sprinkler heads. One says 50 years which is the rule I am familiar with however in the 2002 edition and newer in section 5.3.1.1.1.5 it also states 75 years for replacement. Which one do you usez?.

    Reply
    • Joseph — First, you can read our complete guide to the latest fire sprinkler replacement & testing rules in the 2023 edition of NFPA. NFPA 25 makes a distinction between sprinklers over 50 years old and sprinklers over 75 years old & manufactured in 1920 and later in terms of the subsequent testing or replacement intervals: every 10 years once they hit 50, every 5 years once they hit 75. In either case, they must be tested or replaced at the relevant interval. Here are the references:

      5.3.1.1.1 Where sprinklers have been installed for 50 years, one of the following shall occur:

      (1) The sprinklers shall be replaced.
      (2) Representative samples of the sprinklers shall be tested and then retested every 10 years.

      5.3.1.1.1.4* Where sprinklers have been manufactured in 1920 and later and have been installed for 75 years, one of the following shall occur:

      (1) The sprinklers shall be replaced.
      (2) Representative samples of the sprinklers shall be tested and then retested every 5 years.

      Reply
  3. Should the list of sprinklers referenced in NFPA 25 5.4.1.5.6 be the spares in the cabinet or an inclusive list of everything on the installed in the system?

    Reply
    • John — the spares themselves must reflect every type of sprinkler; if you use more than one kind of head (for instance, if you use both certain quick-response and standard sprinkler heads), you must have at least 2 of each kind. And you need to know the total number of sprinklers in the system to know how many spares you need. So, the best list would be a simple itemization like “100 of (these SINs), 50 of (these SINs), etc.”

      Reply

Leave a Comment