EPS10-2 Alarm Pressure Switch by System Sensor - UL & FM Approved!
- Buy 2 for $86.40 each and save 5%
- Buy 5 for $81.86 each and save 10%
- Buy 10 for $77.31 each and save 15%
Part Number | Mounting | Maximum Operating Pressure | Maximum Adjustment Pressure Range |
---|---|---|---|
ELPS102 | 1/2" (6.35 mm) Male NPT (MNPT) Glass-Reinforced Nylon | 300 PSI | 4 to 20 PSI |
Dimensions | Service Use | Enclosure Rating | Warranty |
---|---|---|---|
5.12" H x 3.325" W x 4.250" L (13.0 cm x 8.4 cm x 10.8 cm) | NFPA 13, NFPA 13D, NFPA 13R, NFPA 72 | Rated UL 4x, NEMA 4 for indoor or outdoor use | 3 Years |
Availability | Listings |
---|---|
Usually ships within 48 hours | UL, ULC, FM, LPCB, CA Fire Marshall, VdS |
Product Description
System Sensor's EPS10-2 Pressure Switch is designed to indicate discharge in water-based systems, including wet, dry, deluge, and pre-action automatic fire sprinkler systems. Featuring a weatherproof NEMA 4-rated enclosure and approvals from UL, ULC, FM, MEA, and California's Office of the State Fire Marshal, this durable Two-Switch Alarm Pressure Switch is suitable for indoor or outdoor use.
System Sensor's EPS10-2 Pressure Switch can be side-mounted or installed in the upright or horizontal position using the 1/2" (6.35 mm) NPT pressure connection. The reinforced diaphragm resists pressure spikes and features a sensitivity adjustment wheel for adjustable actuation pressures between 4 and 20 PSI.
Each alarm pressure switch includes tamper-resistant screws, a security wrench, and two SPDT switches. System Sensor's EPS10-2 Pressure Switch is factory set to trigger local alarms or a fire alarm control panel at pressures between 4 PSI and 8 PSI on rising or falling pressure.
Additional Specifications
Specifications | |
---|---|
Switch Contact Ratings | 10.0 A, 1/2 HP @ 125/250 VAC. 2.5 A @ 6/12/24 VDC |
Cover Tamper Switch | UL Models: Optional P/N 546-8000. ULC Models: Factory Installed. |
Shipping Weight | 1.2 lbs (.54 kg) |
Service Use | NFPA 13, NFPA 13D, NFPA 13R, NFPA 72 |
Technical Documents
Click here to view the data sheet for this System Sensor's EPS10-2 Pressure Switch .