FlexHead | 36" Flexible Sprinkler Drop Assembly | 3/4" NPT | UL & FM Approved

SKU
75FD36
Connect 3/4" NPT fire sprinklers to 1" (25.4 mm) NPT branch lines with this Braided 36" (914 mm) Flexible Sprinkler Drop Assembly. With stainless steel hose, a galvanized steel mounting bracket, and pipe nipples, this FlexHead® assembly is UL & FM Approved and perfect for fast and accurate placement of sprinkler heads in suspended or hard ceilings.
$47.95
SKULengthInletOutlet
75FD3636" (914 mm)1" (25.4 mm) NPT3/4" (19 mm) NPT
FM Equivalent LengthUL Equivalent LengthApprovalsMaximum Working Pressure
1" Schedule 40 Pipe: 21.5 ft @ 8.0K, 21.6 ft @ 11.2K, 21.8 ft @ 14.0K, 10.9 ft @ 16.8K1" Schedule 40 Pipe: 18 Ft.UL & FM Approved175 PSI
Maximum Ambient TemperatureAssembly IncludesAvailability
300F (149C)Hose, Mounting Bracket with Adjustable HubUsually Ships Within 48 Hours

Product Description

Braided 36" (914 mm) Flexible Sprinkler Drop for 3/4" NPT fire sprinklers connects rigid piping to fire sprinkler heads using pliable stainless steel hose, reducing installation time and labor costs. Each FlexHead® 36" (914 mm) durable sprinkler fitting includes a stainless steel braided hose and an adjustable open-port mounting bracket designed to provide perfect center-of-tile placement.

This 36" Flexible Sprinkler Drop is FM approved for two (2) 90-degree bends and UL-listed for three (3) 90-degree bends, facilitating quick and accurate placement of fire sprinklers in drywall ceiling grids, confined spaces, and more. Made by SprinkFLEX LLC, a Massachusetts-based manufacturer of flexible fire sprinkler connections, this drop is all-welded, meets 2013 NFPA 13 guidelines, and is acceptable for use in a return-air plenum.

This commercial fire sprinkler connection features a braided hose and bracket designed to connect 3/4" (19 mm) NPT sprinklers to 1" (25.4 mm) NPT branch lines. The mounting bracket comes preassembled at center tile position and features an open hub for ease of installation.

FlexHead® is a registered trademark of SprinkFLEX, LLC and Anvil International, a North American manufacturer of piping system products.

Technical Documents

Click here to view the data sheet for this Braided 36" (914 mm) Flexible Sprinkler Drop for 3/4" NPT fire sprinklers.