Reliable™ A2361134S8 Product Description
Reliable™ Model F1-80 Pendent Fire Sprinkler Head
Sprinkler Identification Number (SIN): RA6212
The Reliable™ RA6212 pendent sprinkler with a 360°F (182°C) temperature rating is designed for high-temperature environments where standard or intermediate temperature models are not sufficient. With a Standard Response activation and Standard Coverage, it provides dependable performance in areas like boiler rooms, industrial ovens, and heat-processing facilities.
It features a durable Brass finish and is constructed from a robust brass frame and deflector. The glass bulb heat element ensures responsive activation under extreme thermal conditions.
Key Specifications
-
K-Factor: 8.0
-
Connection Size: 3/4 in. NPT
-
Finish: Brass
-
Temperature Rating: 360°F (182°C)
-
Response Type: Standard Response
-
Coverage Type: Standard Coverage
-
Heat Element: Glass Bulb
-
Corrosion Resistance: No
-
Material Composition: Brass Frame, Brass Deflector
Certifications & Listings
-
UL Listed (up to 250 PSI)
-
FM Approved (up to 175 PSI)
-
Also listed by: cULus, LPCB, VdS, CE, and UKCA
Installation & Compatibility
-
Approved Wrenches:
-
Model W2 (standard installation)
-
Model W14 (when installed with guard)
-
-
Approved Guards & Shields:
-
F-2 Guard (FM)
-
F-6 Guard/Shield Kit (FM)
-
F-7 Guard (cULus)
-
F-8 Guard/Shield Kit (cULus)
-
S-2 Shield (cULus, FM)
-
Note: Recessed escutcheons are not listed for use on 286°F or higher temperature models.
Series Overview
The RA6212 is part of Reliable™’s F1-80 pendent sprinkler line and is available in:
-
Finishes: Brass, Chrome, White Polyester
-
Temperature Ratings: 135°F, 155°F, 175°F, 200°F, 286°F, and 360°F