Tyco™ TY-B (TY315) Upright Fire Sprinkler Head
This Tyco™ TY-B Brass Upright Fire Sprinkler features a glass bulb activating at 155F (68C) with a 5.6 K-Factor, and 1/2 in. NPT threads. Each upright head features a bronze frame and bronze deflector. The manufacturer part number is 77-570-1-155, and the Sprinkler Identification Number (SIN) is TY315.
The TY-B Upright Sprinkler delivers effective, affordable defense and is designed for use in light, ordinary, or extra hazard, commercial occupancies such as banks, hotels, shopping malls, factories, refineries, and chemical plants. Using a heat-activated glass bulb assembly, this automatic fire sprinkler opens when ambient temperatures reach 155F (68C), drenching the area surrounding a fire to keep it in its place of origin.
Tyco™ Upright Fire Sprinkler TY-B (TY315) Sprinkler Head Listings and Approvals
Each TY-B sprinkler is made by Tyco™, a global leader in fire-suppression products. This upright fire sprinkler head maintains FM Approval and is UL Listed.
The TY315 is a commercial sprinkler and is cULus listed for use when installed in accordance with NFPA 13 requirements for wet pipe sprinkler systems and designed for use in commercial occupancies. This upright sprinkler head has a maximum working pressure of 175 PSI (12.1 BAR) FM, and is UL Listed for 250 PSI (17.2 bar) and connects to wet piping systems.
Tyco™ TY-B (TY315) Upright Sprinkler Installation and Other Information
During installation be aware that over tightening will cause permanent damage to the 1/2 NPT threads and/or the fire sprinklers themselves. Use the manufacturer approved installation wrench and tighten to a maximum torque of 14 ft-lb (19 N-m). Refer to the data sheet for additional storage and installation information. If an upright sprinkler head is not installed properly, it may not work as intended.
This upright sprinkler features a brass finish and a 155F (68C) temperature. Available finish options include Brass, Chrome, White, and Black. Signal White Polyester (White) and Jet Black Polyester (Black) are UL Listed as corrosion resistant. Temperature options include 135F (57C), 155F (68C), 175F (79C), 200F (93C), 286F (141C), and 360F (182C). Finish and temperature combinations available in the “Options” section at the top of this product page.
TY315 listed accessories include the W-Type 6 sprinkler wrench, manufacturer part number(s) (56-000-6-387). This sprinkler head is commonly purchased with fire sprinkler head cabinets and sprinkler shut off tools. These products are available in the “Frequently bought together” products section at the top of this product page. Over the years, Tyco™ has acquired Central Sprinkler, Gem Sprinkler Company, Grinnell Corporation, and Star Sprinkler Incorporated, and while these brands are no longer available, Tyco™ has re-designated many of their sprinkler models. Standard response sprinklers from Gem and Grinnell’s previous Model A line were incorporated into Series TY-B.