Flame behind a fire sprinkler

The biggest threat to fire sprinklers' performance: the people they protect

More than 90 percent of the time, automatic fire sprinklers operate as expected when an emergency breaks out—controlling or extinguishing flames before they have devastating consequences. But when sprinklers fail, human error is almost always the root of the problem.

In the first installment of our series on the most common mistakes that cause fire sprinkler failure, we examined simple-but-serious errors that involve shutting off the system or manually interfering with its operation. In this blog, we will shine a light on other frequent mistakes, including failing to perform simple maintenance and more complicated errors like installing systems that can’t control the intensity of fires generated by a property’s hazards.

Looking to buy fire protection equipment? Feel free to browse our selection of sprinkler system components and accessories, including commercial and residential sprinkler heads, installation tools, Shutguns that quickly shut down triggered sprinkler heads, heavy-duty head guards that protect sprinklers from accidental damage or vandalism, and more.

Maintaining a fire sprinkler system

Following NFPA 25’s inspection, testing, and maintenance guidelines keeps fire sprinklers in working order and helps catch problems before they lead to system failures.

Lack of regular maintenance is a common mistake that causes fire sprinkler failure

A fire ravaged a Georgia textile recycling plant in 2007, killing one person and causing $7.5 million in damage. This happened even though a fire sprinkler system was installed and more than 75 sprinklers operated in an attempt to control the blaze. So, what went wrong?

According to the Society of Fire Protection Engineers (SFPE), lack of maintenance triggered the tragedy. The plant’s sprinkler system had been neglected for years, with maintenance deficiencies including partially-closed valves that restricted water flow, sprinkler risers modified to allow the use of garden hoses, and improper sprinkler clearances. With so many issues, the system was easily overwhelmed by the fire.

A properly functioning fire sprinkler system can be all that stands between the people and property you want to protect and an out-of-control blaze. Even just a few minutes of delay before sprinklers kick in can lead to devastating consequences.

Following the guidelines specified in NFPA 25: Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems is key to keeping sprinkler components in tip-top shape and catching problems before they lead to system failures. Known as the “wear and tear” document, NFPA 25 details minimum requirements for all inspection, testing, and maintenance (ITM) of fire sprinklers and other systems. It also outlines the process that needs to be followed when problems are found, including proper fixes and reporting.

Fire sprinkler systems can suffer any number of service issues, including closed valves, worn-out parts, corroded pipes, and obstructions to the water supply. Most of these problems can be easily avoided or fixed. But without an ITM schedule, property owners are unlikely to realize they’re occurring until—like that Georgia recycling plant—it’s much too late.

Corrosion, for instance, is a serious concern in any sprinkler system that combines oxygen, water, and metal. More than 70 percent of dry sprinkler systems suffer significant corrosion issues within 12.5 years of installation, according to a Potter Corrosion Solutions report. Wet systems corrode slower, but they don’t escape unscathed: 35 percent experience significant issues after 25 years.

Corrosion quietly rots metal pipes from the inside out, making it nearly impossible to detect until the problem is so severe that the system suffers leaks, obstructions, or accidental sprinkler discharges. Regular inspection of sprinkler pipes helps catch corrosion at its earliest stages, while maintenance activities like system flushing mitigate damage, using a pressurized water source to remove potential blockages.

To learn more about mitigating corrosion in sprinkler pipes, check out our previous blog: “My Sprinkler Pipes are Corroded. Now What?

Corrosion causes fire sprinkler failure

Regular inspection, testing, and maintenance can catch corrosion at its earliest stages, before it eats holes in pipes and causes leaks and fire sprinkler failures. Source: Sprinkler Age

Corrosion is just one example of many things that need to be spotted early. Even far-less-difficult issues, like someone placing storage in a spot that blocks sprinklers’ spray patterns, can have serious consequences—ones that could be easily avoided by doing the annual visual inspection of sprinkler heads required by NFPA 25.

Documenting and exploring the root causes of any issues that are discovered while inspecting, testing, or maintaining sprinklers is key to reliable system performance. NFPA 25 categorizes components that aren’t up to code into three categories to help property owners prioritize repairs: impairments, critical deficiencies, and noncritical deficiencies.

Noncritical deficiencies don’t impact system performance but must be corrected to meet NFPA standards within a reasonable amount of time (3.3.7.2). Critical deficiencies can have a “material impact” on system performance and should be corrected as soon possible (3.3.7.1).

Impairments are the most serious, meaning all or part of the system is out of order and won’t function properly until it’s repaired (3.3.21). These issues are the highest priority and must be addressed immediately.

NFPA 25 requires property owners to maintain careful records of ITM activities performed on their fire sprinkler systems (4.3). These documents must be kept for at least two years so deteriorating performance is easy to spot by comparing results (4.3.5).

From the 2017 edition of NFPA 25

4.3.2 Records shall indicate the following:

(1) The procedure/activity performed (e.g., inspection, test, or maintenance)

(2) The organization that performed the activity

(3) The required frequency of the activity

(4) The results and date of the activity

(5) The name and contact information of the qualified contractor or owner, including lead person for activity

How diligently these records are kept speaks volumes about the property owner or facility manager’s investment in maintaining fire protection. Missing, incomplete, or outdated records can make preventive maintenance virtually impossible—and increase the likelihood of system failures. Without consistent documentation, it may be impossible to know when gauges were last calibrated or changed, for example, or if the fire pump is being run at regular intervals, or whether any past deficiency was ever corrected.

Deluge fire sprinkler system in an aircraft hangar

A deluge sprinkler system protects an aircraft hangar, which carries a more hazardous occupancy classification than common environments. Source: US Army Corps of Engineers

Choosing an inappropriate system for a property’s hazards offers inadequate protection from fire

One of the most important decisions in designing a sprinkler system is determining your property’s occupancy classification. NFPA 13 defines occupancy classifications based on the type of materials a building contains, which impacts how hot fires will burn and how quickly they will spread. Fires develop slowly with low levels of heat in light-hazard properties such as schools or offices but spread quickly and burn extremely hot in severe-hazard environments like aircraft hangars and oil refineries.

A property’s occupancy classification determines the type and number of sprinklers it needs, their orientation, and their spacing within a building. Get these and other elements wrong and your fire sprinklers may not be effective because the amount of water they provide is no match for the hazard.

Hidden factors can influence a property’s classification, such as storing products that can be explosive during a fire. It’s critical to enlist the help of a fire protection professional when determining the hazard level so such factors are discovered during a routine survey instead of an emergency event. When more than one occupancy hazard classification exists in a building, the most hazardous level should apply to the entire structure.

A burned-down building

Make sure your fire sprinkler system is appropriate to the property’s hazard level—and make sure it’s updated when the property changes.

Now read this carefully: A sprinkler system’s effectiveness during a fire is limited by the design criteria of the original installation. Occupancy classification must be revisited any time the use of a building or space within it changes to ensure the sprinkler system still provides sufficient protection.

A common mistake property owners make is failing to re-evaluate and make necessary modifications to sprinklers after modifications are made to a property’s space or utility, even if they seem minor. For instance, if major renovations are completed without redesigning the sprinkler system layout, coverage is almost always inadequate. Even something as simple as a tenant change from a traditional office to a doctor’s office can change hazard levels and require different coverage.

Understanding the original system design and how a building has evolved over time is key to avoiding fire sprinkler failure. Annually reviewing a property’s occupancy classification is wise to ensure the system remains appropriate for the hazards and use of the building, and will protect people and property from fires.

Minor mistakes can have a major impact on the reliability of fire sprinklers

People pose the biggest threat to the effectiveness of fire sprinklers. Thus, understanding the biggest human errors that compromise these systems are your overwhelmingly best bet to ensure they work as intended.

Make sure to read part one of this series to round out your knowledge of common mistakes that cause fire sprinkler failure.

Fire sprinkler

In the market for fire protection? Feel free to browse our selection of sprinkler system components and accessories, including commercial and residential sprinkler heads, installation tools, Shutguns that quickly shut down triggered sprinkler heads, heavy-duty head guards that protect sprinklers from accidental damage or vandalism, and more.