#144 – Restaurant Fire Safety Regulations: The Basics
#144 – Restaurant Fire Safety Regulations: The Basics
Understanding restaurant fire safety regulations protects your property, employees, and customers – and the health of your business
So, you own a restaurant or you’re thinking of starting one? It’s an in-demand business – 39% of adults would like to eat at restaurants more often, and 51% of diners eat out more than once a week, in an industry that does nearly $800 billion in sales annually.
John Taffer, host of the hit show Bar Rescue and author of Raise the Bar: An Action-Based Method for Maximum Customer Reactions, states that it’s “a growth industry and there are plenty of opportunities to make money and create the legacy of smiles if you do it right.” And along with the “right” stuff of smart menu creation, staffing, and restaurant design is making sure you have the appropriate fire protection and life safety measures in place – to protect patrons and property and avoid costly restaurant fire safety violations.
NFPA 101: Life Safety Code provides the requirements for fire protection and life safety based on a building’s occupancy type and occupant load. A medium-to-large-sized restaurant is defined as an “assembly occupancy” and must meet the requirements in chapter 12.
From the 2015 edition of NFPA 101
3.3.190.2* Assembly Occupancy. An occupancy (1) used for a gathering of 50 or more persons for deliberation, worship, entertainment, eating, drinking, amusement, awaiting transportation, or similar uses…
Restaurants having an occupant load of less than 50 are classified as a mercantile occupancy and must meet lesser requirements.
A.3.3.190.2 Restaurants and drinking establishments with an occupant load of fewer than 50 persons should be classified as mercantile occupancies.
The primary difference between assembly and mercantile occupancies are the limitations and allowances for the means of egress – in plain speak, the ways that are available to exit the property in an emergency. There are no requirements for fire sprinklers or fire alarms in smaller spaces. Larger spaces with a much bigger occupant load, however, are required to have them.
To determine what fire protection features are required, establish the total occupant load:
From the 2015 edition of NFPA 101
3.3.164.2 Occupant Load. The total number of persons that might occupy a building or portion thereof at any one time.
Occupant loads are determined by dividing the available floor area square footage by the occupant load factors shown in Table 7.3.1.2 of NFPA 101:

Occupant Load Factor Table. Source: 2015 edition of NFPA 101
This table shows five areas that specifically pertain to restaurant occupant loads. To determine the occupant load, you measure the square footage of a given area and divide it by the allowed square feet per person. For example, a 500 square-foot kitchen would have an occupant load of 5 people, given the maximum of 100 square feet per person listed in the table above. Each type of area should be calculated individually based on the numbers in the above table and then added up. In the end, you will have the total occupant load for the restaurant space.
The following occupant load limitations specific to larger assembly occupancies must be also applied:
From the 2015 edition of NFPA 101
12.1.7.1.1 In areas not in excess of 10,000 sq.ft., the occupant load shall not exceed one person in 5 sq. ft.
12.1.7.1.2 In areas in excess of 10,000 sq.ft., the occupant load shall not exceed one person in 7 sq.ft.
The four types of restaurant fire protection
In general, larger restaurants will require these elements of fire protection:
- A fire sprinkler system
- A fire alarm
- Cooking equipment protection
- Special protection for any hazardous areas
1. Fire sprinkler systems in restaurants
A fire sprinkler system is required in all establishments that are classified as a dance hall, discotheque, or nightclub, or when the total occupant load exceeds 300 persons. Some smaller restaurants still install sprinklers, however, as common wet systems are fairly affordable and lead to vastly greater fire safety, plus discounts on insurance. Any structures that use automatic fire sprinkler systems must install them in accordance with NFPA 13: Standard for the Installation of Sprinkler Systems.
If your building requires a fire sprinkler system, it must also be properly maintained to work properly and pass fire inspections. NFPA 25: Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems describes the requirements for water-based systems.
Many potential code violations are outlined in the two-part QRFS article series: “NFPA 25 - The 10 Most Common Fire Safety System Compliance Issues and How to Avoid Them.”

Pendent fire sprinkler installed in ceiling. You can view pendent sprinklers here. (Image source)
2. Fire alarm
A complete fire alarm system is also required for all assembly occupancies that have an occupant load of 300 or greater. Alarm systems must be installed in accordance with the following NFPA standards:
● NFPA 70: National Electrical Code
● NFPA 72: National Fire Alarm and Signaling Code
The fire alarm signals must be transmitted to a location that is constantly attended while the building is occupied. If the provision of a "constantly attended location" is impractical, the local fire authority (AHJ) can require the system to be monitored by an off-site supervising station.

A fire alarm panel and components. Source: The Code Coach
A fire alarm panel can, at first glance, seem intimidating. Demystify a panel and its operations by reading this blog post: “What is a Fire Panel and How Does It Work?”
3. Cooking equipment protection
All cooking equipment used in a commercial application is required to have specific protection. NFPA 96: Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations outlines the full requirements for fire protection. Minimum requirements include a hood and duct system with cooking equipment placed beneath it. A fire extinguishing system is required to be installed within the hood and an exhaust duct system must remove flammable, grease-laden vapors.
From the 2017 edition of NFPA 96
10.1.1 Fire-extinguishing equipment for the protection of grease removal devices, hood exhaust plenums, and exhaust duct systems shall be provided.
10.1.2 Cooking equipment that produces grease-laden vapors and that might be a source of ignition of grease in the hood, grease removal device, or duct shall be protected by fire-extinguishing equipment.
10.1.3 Fume incinerators, thermal recovery units, air pollution control devices, or other devices installed in the exhaust duct, shall be protected by an automatic fire-extinguishing system.

A kitchen hood and suppression system. Source: Federal Fire Protection
4. Special protections for hazardous areas
The Life Safety Code defines several areas of structures as hazardous. These locations are required to be separated from the rest of the building by a minimum of one-hour fire-resistance-rated construction or protected by an automatic fire extinguishing system. These are rooms or areas that include:
● Boilers and furnaces
● Refrigeration machinery (other than domestic)
● Electric transformers
● Service equipment subject to explosion
● Storage of combustible supplies
● Storage of hazardous materials or flammable or combustible liquids
Other particularly-hazardous areas such as laundries, maintenance shops, rooms used for the processing of hazardous materials, and spaces used for the processing of flammable or combustible liquids are required to be separated by a minimum of one-hour fire-resistance construction and an automatic fire extinguishing system. These areas are less common in restaurants but if any apply, you must comply with this extra protection standard.
Fire safety is essential in a successful restaurant
Current statistics tell us that most restaurants will close during their first year of operation and that the 70% that make it past year one will close within three to five years. The 90% of restaurants in operation past five years will last for at least 10 years, however. Incorrectly installed fire protection or life safety systems – or a lack of them altogether – shouldn’t be why a restaurant fails.
Taffer says, “you have a serious responsibility to provide a safe space. The public places its trust in establishments and that trust should be honored.”
Providing and properly maintaining fire protection systems and complying with restaurant fire safety regulations will protect property and patrons in an emergency and keep you from running into expensive code violations.
To learn more about the top fire code violations cited by local government inspectors, read this blog.
If you need to replace fire sprinklers and you aren’t sure what you need, read this comprehensive guide.
And if you are looking to buy system components, browse QRFS’s wide selection or contact us at 888-361-6662 or [email protected] with any questions.