Globe Pipe Hanger Swivel Ring | 2 1/2" Swivel Ring 304-230

SKU
SWV250
2 1/2" (63.5 mm) Globe Pipe Hanger Swivel Ring suspends non-insulated 2 1/2" (63.5 mm) stationary pipe in fire-protection and plumbing systems with 3/8 in. rod sizes.
$1.99
Part NumberPipe SizeMaterialRing Height
SWV2502 1/2" (63.5 mm)Carbon Steel5 1/2"
Clearance (Pipe to Nut)Maximum Recommended LoadFinishWeight
1 3/8"600 PoundsPre-Galvanized4.8 Ounces Each
Globe Part NumberAvailabilityAvailability
300-224UL & FM ApprovedUsually Ships Within 48 Hours

Product Description

2 1/2" (63.5 mm) Globe Pipe Hanger Swivel Ring is designed for the suspension of non-insulated stationary pipe lines in fire sprinkler systems, standpipes, plumbing, and other piping applications. This steel hanger is designed for 2 1/2" (63.5 mm) pipes and has a maximum recommended load of 600 Pounds

Each 2 1/2" (63.5 mm) Swivel Ring features a zinc electroplate nut that allows for vertical adjustment after installation. In accordance with NFPA 13 9.1.1.2 (2016), hangers for fire protection piping must be rated for 5 times the weight of water-filled pipe plus 250 pounds at each support. This swivel ring may be installed prior to the erection of piping.